Installing the indoor unit
Total weight with filled DHW cylinder
Vitocal 222-S
230 V appliances
400 V appliances
Each pressure point (each with an area of 3217 mm
is subject to a load of up to 96 kg.
Connecting the refrigerant lines
The outdoor unit is pre-charged with refrigerant
R410A.
Oil lift bends
Oil lift bends guarantee that the refrigerant oil is relia-
bly conveyed back to the compressor.
!
Please note
Errors in the design and installation of oil lift
bends can result in appliance damage.
In the following cases, fit oil lift bends in the ver-
tical hot gas line:
In heating mode, if the indoor unit is installed
higher than the outdoor unit.
In cooling mode, if the indoor unit is installed
lower than the outdoor unit.
Distance between the oil lift bends approx.
5 m.
(cont.)
Type
AWBT-M
AWBT-M-E
AWBT-M-E-AC
AWBT
AWBT-E
AWBT-E-AC
2
)
221.C04
221.C06
221.C08
221.C10
221.C13
221.C16
221.C10
221.C13
221.C16
Indoor unit above outdoor unit
A
C
B
E
Fig. 19
Example for heating mode: With oil lift bends
Indoor unit
A
Hot gas line (hot gas)
B
Liquid line (liquid)
C
Outdoor unit
D
Oil lift bends
E
Installation sequence
Total weight in kg
382
382
382
383
383
383
383
383
383
D
23