Coding level 2
(cont.)
Coding in the delivered condition
31:...
Set speed of the internal circula-
tion pump when operated as boiler
circuit pump in %, specified by the
boiler coding card
38:0
Burner control unit status: Opera-
tional (no fault)
49:0
No CO limiter installed.
Must be set if the CO limiter is to
be connected and automatically
activated.
Group 3
Select "3" (see page 46).
Coding
Coding in the delivered condition
05:0
No DHW cylinder
Possible change
31:0
Set speed adjustable from 0 to
to
100 %
31:100
38:≠0
Burner control unit status: Fault
49:1
CO limiter with sensor monitoring
and fault message active.
Is set automatically during commis-
sioning if the CO limiter is connec-
ted.
49:2
CO limiter active
If the CO limit is exceeded:
CO limiter sounds an alarm
■
Alarm signal is not transmitted to
■
the control unit
The burner is not switched off
■
No fault message to the control
■
unit
Note
Coding addresses 05, 09, 19 and 1A can only be set
for gas condensing system boilers.
Possible change
05:1
One mono mode DHW cylinder
05:2
One mono mode DHW cylinder
05:3
One dual mode DHW cylinder
05:4
Vitocell 100-W, type CVUC-A
05:5
Do not adjust
05:6
Vitocell 100-W, 100-B, type CVB,
300 l
05:7
Vitocell 100-W, 100-B, type CVB,
400 l
05:8
Vitocell 100-W, 100-B, type CVB,
500 l
05:9
Vitocell 140-E, type SEIA, 400 l
05:10
Vitocell 140-E, type SEIA, 600 l
05:11
Vitocell 140-E, type SEIA, 750 l
05:12
Vitocell 140-E, type SEIA, 950 l
05:13
Vitocell 160-E, type SESA, 750 l
05:14
Vitocell 160-E, type SESA, 950 l
05:15
Vitocell 340-M, type SVKA, 750 l
05:16
Vitocell 340-M, type SVKA, 950 l
05:17
Vitocell 360-M, type SVSA, 750 l
05:18
Vitocell 360-M, type SVSA, 950 l
Codes