Coding level 1
(cont.)
Coding in the delivered condition
Extended solar control functions
20:0
No extended control function ena-
bled

Group 5

Select "5" (see page 42).
Coding
Coding in the delivered condition
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for weather-
compensated control units)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
Pump control in "Only DHW"
F6:25
In "Only DHW" operating mode,
the internal circulation pump is per-
manently on.
Pump control in "Standby mode"
F7:25
In "Standby mode", the internal cir-
culation pump is permanently on.
Possible change
20:1
Auxiliary function for DHW heating
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and auxiliary function.
20:4
Differential temperature control 2 for
central heating backup.
20:5
Thermostat function
20:6
Thermostat function and auxiliary
function
20:7
Solar heating via external heat ex-
changer without additional tempera-
ture sensor
20:8
Solar heating via external heat ex-
changer with additional temperature
sensor
20:9
Solar heating of 2 DHW cylinders
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
F6:0
In "Only DHW" operating mode, the
internal circulation pump is perma-
nently off.
F6:1
In "Only DHW" operating mode, the
to
internal circulation pump is started 1
F6:24
to 24 times per day for 10 min each
time.
F7:0
In "Standby mode", the internal cir-
culation pump is permanently off
F7:1
In "Standby mode", the internal cir-
to
culation pump is started 1 to
F7:24
24 times per day for 10 min each
time.
Codes
45