Table of Contents

Advertisement

Installation

Connect Power

Power
Connect
Connect
Power
Improper wiring may cause electric shock, fire
and explosion, or other serious injury if work
is not performed properly. Have a qualified
electrician perform any electrical work. Be sure
your installation complies with all National, State
and Local safety and fire codes.
1. Shut off the fused safety switch (B) and follow
the appropriate lock-out/tag-out procedures.
Typical fixed installation for wall mounted
systems shown below:
Disconnect Block
Block Terminals
Disconnect
Disconnect
Block
Tighten disconnect block terminals to 7 in-lb
1
(0.8 N•m). Do not over-tighten.
Tighten cover screws to 15 ft-lb (20.3 N•m).
A conduit seal (D) is required within 18 in.
(457 mm) of the driver for the US and Canada.
15 in-lb maximum (terminal bushings)
2. To install wiring, locate the electrical junction box
(Y). Remove four screws (J) and junction box
cover (Z). Wires will already be installed in the
front side of the disconnect in terminals labeled
1L1 and 3L2.
3. Connect the ground wire to the labeled ground
screw in the back of the junction box. See
Grounding, page 9
10
Terminals
Terminals
.
4. Install incoming power wires into the disconnect
terminals labeled 2T1 and 4T2, and torque to 7
in-lb (0.8 N•m).
5. Reinstall junction box cover (Z) and screws (J).
Torque screws to 15–20 ft-lb (21–27 N•m).
NOTE: One wire is installed in terminals 1L1 and
NOTE:
NOTE:
3L2.
Make sure wires are not pinched when
re-installing covers. Wires will be damaged
and create an electrical hazard and/or fire and
explosion hazard if pinched.
† Conduit not supplied.
‡ Power cord not supplied.
3A3165H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ex45

Table of Contents