Specification Specification, Type Bw 301.B090 To Bw 302.B250 - Viessmann KWT Vitocal 300-G Pro Installation And Service Instructions Manual

Table of Contents

Advertisement

Specification
Specification, type BW 301.B090 to BW 302.B250
Operation: brine/water
Type BW
Output data to EN 14511 (B0/W35, 5 K
spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance
(COP)
Brine (primary circuit)
Content
Nominal flow rate to
EN 14511
Minimum flow rate (5 K
spread)
Pressure drop
Max. flow temperature
Min. flow temperature
Heating water (secondary
circuit)
Content
Nominal flow rate to
EN 14511
Minimum flow rate (10 K
spread)
Flow pressure drop (at mini-
mum flow rate)
Flow temperature at min. pri-
mary circuit flow temperature
0 °C
Flow temperature at min. pri-
mary circuit flow temperature
+5 °C
Operation: water/water with intermediate circuit
Type BW
Output data to EN 14511 (W10/W35,
5 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance
(COP)
88
Single stage 301.
B090
kW
93
kW
74.5
kW
19.5
4.77
ε
l
33.0
m
/h
24.5
³
m
/h
15.0
³
mbar
120
°C
20
°C
5
l
22.7
m
/h
16.0
³
m
/h
8.0
³
mbar
100
°C
55
°C
60
Single stage 301.
B090
kW
125
kW
104.5
kW
21
5.95
ε
Two-stage 302.
B120
B090
B120
121
89.4
117.2
96.4
72
93.8
24.8
18.3
24.4
4.83
4.88
4.8
42.0
33.0
42.0
31.7
24.0
31.3
19.0
14.5
18.8
120
120
120
20
20
20
5
5
5
28.7
22.7
28.7
21.0
15.4
20.3
10.5
7.8
10.2
100
100
100
55
60
60
60
65
65
Two-stage 302.
B120
B090
B120
152
118.8
153.0
128
101
129.0
25.6
18.9
25.3
5.93
6.2
6.05
B150
B180
B250
150
182
240
120.1
145.4
191.4
31.9
39.6
50.4
4.70
4.60
4.76
55.2
69.0
89.4
39.5
47.8
62.9
24.0
30.0
39.0
130
140
180
20
20
20
5
5
5
38.7
53.5
57.1
25.8
31.4
41.4
12.9
15.7
20.7
100
100
120
55
55
55
60
60
60
B150
B180
B250
198
235
302
168
197
252
32.1
41
51.8
6.10
5.73
5.83