Siting; Installation Room Requirements - Viessmann KWT Vitocal 300-G Pro Installation And Service Instructions Manual

Table of Contents

Advertisement

Delivery and installation
Information regarding transport with fork lift truck
Select a fork length in line with the heat pump length,
see "Specification" (page 92).
The heat pump's centre of gravity is at the back, by
the hydraulic connections.
Observe required edge protection (e.g. 2 or 3 layers
of corrugated cardboard)

Siting

Installation room requirements

!
Please note
The installation room must be dry and free from
the risk of frost.
Ensure ambient temperatures between 0 and
35 °C.
!
Please note
Avoid risks of explosion due to dust, gases and
vapours
in the installation room.
!
Please note
Observe the permissible floor load.
Total weight, type BW 301.B090 to
BW 302.B250:
BW 301.B090 700 kg
BW 301.B120 800 kg
BW 302.B090 705 kg
BW 302.B120 810 kg
BW 302.B150 1130 kg
BW 302.B180 1190 kg
BW 302.B250 1300 kg
Total weight, type WW 301.B125 to
WW 302.B300:
WW 301.B125 1015 kg
WW 301.B155 1055 kg
WW 302.B125 1035 kg
WW 302.B155 1060 kg
WW 302.B200 1330 kg
WW 302.B250 1380 kg
WW 302.B300 1425 kg
(cont.)
Note
Transport by fork lift truck is only permitted without fit-
ted side panels and front or back panels.
To prevent the transmission of structure-borne noise,
never site the appliance on ceilings with wooden
joists (e.g. in the attic).
Level the appliance.
Where floors are uneven, distribute the load evenly
across the adjustable feet.
Observe minimum room volume (to EN 378).
Note
Additional, country-specific regulations apply.
Minimum room volume, type BW 301.B090 to
BW 302.B250:
BW 301.B090 54 m
3
BW 301.B120 68 m
3
BW 302.B090 53 m
3
BW 302.B120 68 m
3
BW 302.B150 86 m
3
BW 302.B180 103 m
3
BW 302.B250 122 m
3
Minimum room volume, type WW 301.B125 to
WW 302.B300:
WW 301.B125 42 m
3
WW 301.B155 49 m
3
WW 302.B125 42 m
3
WW 302.B155 49 m
3
WW 302.B200 59 m
3
WW 302.B250 65 m
3
WW 302.B300 73 m
3
Observe the required floor area and minimum clear-
ances (see following chapter).
Preparing for installation
11

Advertisement

Table of Contents
loading