Rinnai RHFE-951ETR Installation Manual page 16

Power flued flamefire space heater co-axial flue system
Hide thumbs Also See for RHFE-951ETR:
Table of Contents

Advertisement

The joints between ESPIPE900 lengths MUST BE secured by a pop rivet or screw through the
outer Co-ax pipes and flue pipes are to be clipped to the wall using the stand off clips supplied or
CAUTION
other suitable method. ASPKIT03 and ESPIPE900 DO NOT require cutting to be joined.
I n t
e r i
o r
w a
5
l l
5. Create the wall penetration(s) in accordance with the section "WALL PENETRATIONS" on page 8.
The minimum diameter required for wall the penetration for ESPIPE900 is 80mm.
Allow for a continuous 2° fall from the heater connection point from to the wall penetration.
6. Slide the internal wall plate supplied with ASPDFK over the length of ESPIPE900 penetrating the wall at the
internal wall end. Then pass the assembly through the internal wall penetration.
7.
Fasten the internal wall plate to the internal wall.
8. Create the wall terminal in accordance with "ASSEMBLING WALL TERMINAL ~ ASPDFK & ESPIPE900" on
page 20.
9. Move the heater into place and make the heater exhaust and combustion air hose connections in accordance
with the section "CONNECTING CONDENSATE DRAIN KIT TO HEATER" on page 23.
Air hose and heater exhaust connections at the heater MUST be made and checked in accordance
with these instructions. Improper connections may result in dangerous situations, for example, the
CAUTION
dispersion of combustion products in the space being heated.
10. Refere to the chapter "Heater Installation" in the "Rinnai Operation / Installation Manual" supplied with the heater
and complete the installation and commissioning of the heater in accordance with these.
Use ONLY the supplied silicone based "O Ring" seal lubricant. DO NOT use petroleum based lubricants such
as petroleum jelly. The use of petroleum jelly, vaseline
deterioration of the "O Ring" seals.
ONLY use PVC cement between externally located joints of the outer PVC pipes to secure and
seal these joints against ingress of dust and water.
CAUTION
ONLY use non acidic silicone sealant between externally located joints of PVC flue pipe and
any mating aluminium components (such as the condensate trap) to secure and seal these joints
against ingress of dust and water. Silicone containing acetic acid, (characteristically having a
vinegar odour), as the curing agent or other acids may cause corrosion of aluminium components
and MUST NOT be used.
Rinnai
FLUE COMPONENT ASSEMBLY
6
I n t
e r i
o r
w a
l l
Internal wall plate
®
or similar petroleum based lubricants will cause rapid
16
I n t
e r i
o r
w a
7
l l
POWER FLUED FLAMEFIRE FIM