Selection key
4
for heat
recovery mode
Temperature
5
setting key
4.9.2 Setting function
4.9.2.1 System time and date setting function
Function keys:
Cooke Industries - Phone: +64 9 579 2185
Operation instructions of wire controller
Precondition: under daily display state or mode setting state:
1) Press any mode setting key to enter the mode setting state;
2) Display the "SET" icon
3) Short press the
icon will flash;
4) Do not input anything within 10 seconds or short press the
key to confirm the current operation and return to the daily display
state;
Short press the
daily display status.
Prerequisites: In the daily display status, mode setting status or target water
temperature setting status:
1) Press the temperature setting key to enter the target water-temperature
setting state, and the temperature value will flash;
2) Display the "SET" icon
display the current setting temperature;
3) Short press the
the maximum value shall not exceed the maximum limit value;
4) Short press the
the minimum value shall not exceed the minimum limit value;
5) Short press the
temperature for system's chilled water) and HOT WATER (system's
cooling water temperature);
6) Backwater control for refrigeration water; setting range: 10.0~30.0°C;
7) Backwater control for heating water; setting range: 20~50°C;
8) Outflow water control for refrigeration water; setting range: 5.0~
24.0°C;
9) Outflow water control for heating water; setting range: 25~55°C;
10) Backwater control for refrigeration water - saline water; setting range:
-5.0~20.0°C;
11) Outflow water control for refrigeration water - saline water; setting
range: -10.0~15.0°C;
12) Temperature of the hot water tank; setting range: 30.0~55.0°C;
13) Do not input anything within 10 seconds or short press the
to confirm the current operation and return to the daily display state;
14) Short press the
to the daily display status.
,
,
,
,
37
Email: sales@cookeindustries.co.nz
key and the heat recovery
key to cancel the current operation and return to the
key to increase 1 degree of the temperature, and
key to decrease 1 degree of the temperature, and
key to switch between AC WATER (target
key to cancel the current operation and return
,
of the temperature display area;
in the temperature display area and
Web: www.cookeindustries.co.nz