Siemens MD720-3 Manual page 16

Sending and receiving of text messages via serial cps/cms and gprs/gsm modem
Hide thumbs Also See for MD720-3:
Table of Contents

Advertisement

Table of contents
Status
16#8106
16#8107
16#8108
16#8109
16#8110
Note
Errors that do not have a 16#81xy status, are error codes from the
system-internal communication blocks (e.g. S_RECV). (see online help V13)
Note
If the support does not lead to the desired result, it may be useful to load the
MD720-3 factory settings. To do so, use a paper clip. Press the SET button until
the "C" LED lights up and then remove the paper clip.
Note
Once the MD720-3 has been initialized, all SMS messages stored in the buffer
will be deleted.
Sending and Receiving SMS Messages with MD720-3
Entry ID: 25545680,
V1.0,
Meaning
The watchdog timer has expired during
sending because:
3.
The recipient's telephone number is
incorrect
4.
Communication between the
controller and the modem is
interrupted during sending
The previous job has not been completed
yet. (You have started a new send
operation, although BUSY was still
active)
Error while reading the SMS message
The modem must be initialized. (This
error occurs if the modem has not yet
been initialized and you have started a
send operation.)
The watchdog timer has expired during
polling because:
Communication between the
controller and the modem is
interrupted
Too many SMS messages are
stored in the buffer
12/2013
Support / Remarks
Check the parameters and, if
necessary, change them
(recipient's telephone
number)
Check the cable between the
controller and the modem
Restart initialization
Then restart sending.
Restart initialization
Restart initialization
Restart initialization
Then restart sending.
Check the cable between the
controller and the modem
Change the
"TIMER_CHECK" time in the
instance DB of SMS_sr_xxxx
Restart initialization