Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 70

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
or
1
CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
Extinguishing System Outputs
ESE
Extinguishing System Trigger
(not monitored /not disabled by
FWP4)
EST
Extinguishing System Trigger
(not monitored)
ESO
Extinguishing System Output
(monitored)
RLE
Relay Output Module (not
monitored /disabled by FWP4)
CTE
Control
Output
(monitored for open and short
circuits /disabled by FWP4)
997-457-000-8, Issue 8
January 2010
If no device is found at the selected address, the LCD
2
displays one of the messages below:
[Sensor]
[Module]
A specific address can only be configured if:
a. A device has previously been auto-learnt at the
address, or
b. The off-line tool was used to configure the device type
present.
Sensors
The following sensor configuration settings are selectable:
a. The assigned zone (see Section 5.6.1.1, Zone Setting),
b. The sensor sensitivity (see Section 5.6.1.2, Sensor
Sensitivity Setting), and
c. The device text string (see Section 5.8, Zone Texts).
[Sensor nn - AAA] 1 : Zone (nn)
3 : Sensitivity
Input Modules
The following input module configuration settings are
selectable:
a. The assigned zone (see Section 5.6.1.1, Zone Setting),
b. The type of input device (MCP, DKM, MON, ZMX, MNS,
MRL, IRL; Extinguishing System inputs: AUX - Hold Switch
and Abort Switch (see Section 5.6.1.3, Type Setting),
Note: The AUX device types CANNOT be changed.
c. The device text string (see Section 5.8, Text Editing).
[Module nn - AAA] 1 : Zone (nn)
3:CBE Rule (nn) 4 : [
Output Modules
The following output module configuration settings are
selectable:
a. The assigned zone (see Section 5.6.1.1, Zone Setting),
b. The type of output device (SDR, SDH
EST
Section 5.6.1.3, Type Setting).
Sounders enabled with high-load monitoring function.
1
2
These output device types are subject to extinguishing
system disablement if the option to automatically
disable transmission and extinguishing system
devices is configured (refer to Section 5.5.3.14 TD/
Module
ES Disablement at Access Level 2).
c. The CBE Rule number. It is NOT possible to change
the configuration of the associated CBE Rule.
66
Snn (xxx) No device learnt
Mnn (xxx) No device learnt
4 : [
Blank/Existing Text
Blank/Existing Text
, ESO
, ESM, TxD, ESE
2
2
2
]
2 : Type
]
, CTL, RLY,
1
, RLE
and CTE
) (see
2
2