Sounder Circuit Outputs A And B - Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
EN 54-2 : 7.8
If an EN54-2 monitored
fire alarm routing
output is required an
unmonitored relay is
not suitable - use a monitored routing
output.
A
+
A
+
TB1
EOL
997-457-000-8, Issue 8
January 2010

4.4.4 Sounder Circuit Outputs A and B

The sounder cicuits are designed to work either with a
resistor end-of-line (EOL) device (default) or, to comply with
the requirements for partial shorts and open monitoring
of EN54-13 (Compatibility Assessment of System
Components), where a diode EOL device is required. If
resistor EOL devices are to be used follow the first procedure
described below. If diode EOL devices are to be used refer
to the prpcedure described overleaf.
4.4.4.1 Using Resistor EOL Devices
Before the sounder circuits are connected it is
recommended that all detection circuits have been
checked and that there is no possibility of spurious alarm
conditions being generated. The sounders should be
B
polarized and suppressed using IN4002 (or similar)
diodes and the circuits should be fitted with 6k8 end-of-
line resistors. Perform the following checks:
-
+
-
1 Use a low-voltage multimeter to check the resistance
B
-
+
-
2 If electronic sounders are used this test will not reveal
3 When the output circuits have been connected, they
26
across each of the sounder circuits:
i
With the meter connected in reverse polarity (+ve
to -ve and -ve to +ve) the reading should be 6k8.
ii With the multimeter connected to the circuit in
normal polarity (+ve to +ve and -ve to -ve) the meter
may indicate a lower value. This is because of the
forward-biased diodes in series with the sounders.
reversed devices. It is, therefore, recommended that
if the circuit resistance appears correct, the following
be done:
i
Remove the 6k8 resistors from the panel outputs.
ii Connect the circuit to the panel output while
observing correct polarity.
iii If there are any reversed devices the panel will then
indicate:
'Sounder cct. n SHORT-CCT.'.
may be tested using the 'END DELAYS / EVACUATE'
pushbutton.
i
Press the 'END DELAYS / EVACUATE' pushbutton
to activate the Output circuits.
ii Press the 'SILENCE SOUNDERS' pushbutton to
silence all activated output circuits.
iii If the outputs operated correctly press the 'RESET'
pushbutton. If not, check all possible causes and
correct any faults that exist, then repeat Step 3.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id61

Table of Contents