ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
* The Notifier Loop and Battery
Calculator
Support Tool, should be
5
used to ensure that the system is NOT
overloaded.
** Use the following loop driver source
impedance values for panel calculation
purposes: 3.8R at 22.5Vdc
5
The panel (software version 5.04, or later)
is compatible with the Loop Booster
Module (LBM). The LBM provides
additional power to the loop for output
modules during panel alarm conditions.
Refer to the instructions (997-509-000-X)
provided with the LBM for a complete
technical specification.
997-457-000-8, Issue 8
January 2010
Outputs:
a. One Sounder or ÜE drive output (menu selectable -
ÜE not used in this application).
b. One dedicated Sounder output.
c. Two Sounder or Volt-Free Contact (VFC) outputs
(selectable).
d. Two open drain (switched -VE) outputs.
e. One loop output.
f.
One DC auxiliary output (two sets of terminals).
Sounder Output Rating
Type:
Output voltage:
Maximum load:
Fuse rating:
Monitoring:
Volt-free Contact (VFC) Output Rating
Type:
Maximum load:
Fuse rating:
Switched -VE Output Rating
Output voltage:
Maximum load:
Loop Output
Output voltage:
Maximum load*:
Max. loop impedance**: 20 ohms (-ve cable only, with
Max. loop capacitance: 0.5μF
Up to 198 loop devices (up to 99 sensors and 99 modules) may
be fitted to the analogue loop.
The communication with devices on the loop can use either the
Notifier 'CLIP' or OPAL polling protocol. Refer to Hardware
Recommendations for a list of compatible devices and loading
limitations.
RS485 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Maximum cable length: 1200metres (minimum of 1.5mm
A1 - 4
Voltage reversal.
20 to 28V (when active)
700mA per sounder - 1A total
across all four sounder circuits.
Electronic over-current protection.
Open- and short-circuit with
resistor EOL device. Partial-open
and parial-short-circuit with diode
EOL device fitted.
Single-pole change-over
Contacts rated 30V 1A
Not applicable
20 to 28V
83mA (total for both outputs)
22.5 to 26.4V
0.5A
duplicate address detection) or
40 ohms (-ve cable only, without
duplicate address detection).
Functional at 30V.
1200 Baud.
Terminal block on RS485 Isolated
Interface PCB.
screened cable recommended)
2