CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
3
or
2
6
4 Enter a delay time using the numeric buttons, between
0 and 999 secs, e.g. 90 secs:
[Setup]
Enter new value 90
Note: Entering a value of '0' means that the output, after
5 Press the '
Setup menus.
5.5.3.10
AUX modules, configured as one of four Hold Switch
categories, can be used to affect the Extinguishing
System Delay timer function. The four categories are:
AHJ - While this input is active, the Extinguishing System
Delay timer is reset to the configured value and paused.
NYC - While this input is active, the Extinguishing
System Delay timer is reset to the configured value plus
90 secs and paused.
ULI - While active, the Extinguishing System Delay
timer continues to count down but pauses at 10 secs
before release.
IRI - Hold switch activity is ignored if two or more zones
associated with CBE rules with a category of
'Extinguishing System' are in alarm. Otherwise operation
is the same as type ULI.
Note: Only one of the above Hold Switch input types may
1 From the Setup menu screen, press the '
the numeric keypad to enter the Device Options menu.The
Device Blinking screen is displayed first.
[Setup]
> : Change
8
2 Press the '
Options until the LCD shows the Hold Switch
Operation menu.
[Setup]
> : Change
3 Press the '
NYC, ULI or IRI, as required. Changing the setting
saves the change automatically.
Note: The default selection is AHJ.
4 Press the '
Setup menu screen.
5.5.3.11
The Transmission Device activates in response to an
alarm condition. The 'Transmission Device' menu enables
the configuration of either a continuous or a 6 second
49
Ext. System Soak =
: Confirm
switching ON, is not switched OFF.
' button to confirm and return to the
5
Hold Switch Operation
be used per panel.
Device Blinking = ON
: More
/
' buttons to step through the Device
2
8
Hold Switch Operation =
: More
' button to select alternative settings of
6
' button to confirm and return to the
5
Transmission Device
0 Seconds
< : Cancel
' button on
3
< : Exit
AHJ
< : Exit
997-457-000-8, Issue 8
January 2010