Programming

Special Purpose Zone

Pressing 3 for Special Purpose, while viewing Zone Setup Screen #1, will display the following screens:
Zones 047, 048, 049, and 046 (and Zones 094 and 095 in Canadian mode) can be programmed for normal zone operation or for special pur-
pose applications. In the above illustration, the four zones are shown Off, which means they can be programmed to function in the same
manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 47 On. Each press of the 1 key will cause the display to toggle between PAS 47 On and
PAS 47 Off. When Zone 047 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 047 to
activate. By assigning Zone 047 to a control module in the Programming Zone Assignment Screen, an output device connected to the control
module can be used to indicate a PAS condition in the control panel. Do not assign Zone 047 to a Notification Appliance Circuit when using
this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 2 will cause the display to change to Pre-signal 48 On. Each press of the 2 key will cause the display to toggle between Pre-signal
48 On and Pre-signal 48 Off. When Zone 048 is programmed On, a Pre-signal activation of any device will cause Zone 48 to activate. By
assigning Zone 048 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can
be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 048 to a Notification Appliance Circuit when using this
zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 49 On. Each press of the 3 key will cause the display to toggle between Two Stage
49 On and Two Stage 49 Off. Refer to "Two Stage Operation" on page 75 for a description of this feature. Two-stage operation cannot be
used at the same time as in-suite silence feature.
Pressing 1 while viewing the Special Purpose Zone Screen #2 will cause the display to change to Local Alm 46 On. Each press of the 1 key
will cause the display to toggle between Local Alm 46 On and Local Alm 46 Off. When Zone 46 is programmed On, a Local Alarm activa-
tion of any smoke detector will cause Zone 046 to activate. By assigning Zone 046 to a control module in the Programming Zone Assign-
ment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control panel. Local
Alarm Zone alarms are not reported to the Central Station.
When the panel is set to Canadian mode, pressing 2 while viewing the Special Purpose Zone Screen #2 will cause the display to change to
CO Active 45 On. Each press of the 2 key will cause the display to toggle between CO Active 45 On and CO Active 45 Off. When enabled,
this zone will activate when a CO Alarm is active on the panel without requiring direct zone mapping to an input device.
When the panel is set to Canadian mode, pressing 3 while viewing the Special Purpose Zone Screen #2 will cause the display to change to In
Suite Sil 44 On. Each press of the 3 key will cause the display to toggle between In Suite Sil 44 On and In Suite Sil 44 Off. When enabled, this
zone works in conjunction with the In Suite Silence Timer. When enabled, this zone will activate only when a fire alarm is active on the
panel and will not activate via zone mapping to an input device. When the In Suite Silence Timer expires, all silenceable output devices and
NACs that are activated by only the In Suite Silence Zone will silence. If an output or NAC is activated by a general zone and the In Suite
Silence Zone, the output or NAC will not silence when the In Suite Silence Timer expires. This timer restarts with each new fire alarm that
occurs on the system. If the timer expires, all silenced outputs and NACs that were silenced by the In Suite Silence Timer will resound with
a new fire alarm and the In Suite Silence Timer will restart. In-suite silence cannot be used at the same time as two-stage operation.

Zones Installed

ZONE SETUP
1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED
Zone Setup Screen #2
This display will show all of the zones that have been programmed into the control panel. Note that an up and/or down arrow may appear in
the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view
the additional zones.
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
66
SPECIAL PURPOSE
1=PAS 47
OFF
2=PRESIGNAL 48
OFF
3=TWO STAGE 49
OFF
Special Purpose Zone Screen #1
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the follow-
ing:
ZONES INSTALLED
000 001 002 003 004
005
Zones Installed Screen
ZONES ENABLED
000 001 002 004 005
006 007 008 009 010
011 012 013 014
Zones Enabled Screen
SPECIAL PURPOSE
1=LOCAL ALM 46
OFF
2=CO ACTIVE 45
OFF
3=IN SUITE SIL 44 OFF
Special Purpose Zone Screen #2
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021