Transmitter with ultrasonic time-of-flight sensor (36 pages)
Summary of Contents for Endress+Hauser Proline 500 digital PROFIBUS DP
Page 1
Products Solutions Services KA01390D/06/EN/01.18 71402582 Brief Operating Instructions Proline 500 – digital PROFIBUS DP Transmitter with Coriolis sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter.
Page 2
Proline 500 – digital PROFIBUS DP Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Page 3
These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
Result of a step Visual inspection 1.1.3 Electrical symbols Symbol Meaning Symbol Meaning Direct current Alternating current Direct current and alternating current Ground connection A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system. Endress+Hauser...
Page 6
Allen key Open-ended wrench 1.1.6 Symbols in graphics Symbol Meaning Symbol Meaning 1, 2, 3,... Item numbers … Series of steps A, B, C, ... Views A-A, B-B, C-C, ... Sections Hazardous area Safe area (non-hazardous area) Flow direction Endress+Hauser...
Danger of breakage due to corrosive or abrasive fluids and ambient conditions! ‣ Verify the compatibility of the process fluid with the sensor material. ‣ Ensure the resistance of all fluid-wetted materials in the process. ‣ Keep within the specified pressure and temperature range. Endress+Hauser...
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. IT security Our warranty is valid only if the device is installed and used as described in the Operating Instructions.
The transmitter and sensor are mounted in physically separate locations. They are interconnected by a connecting cable. Transmitter Connecting cable: cable, separate, standard Sensor connection housing with integrated ISEM (intelligent sensor electronics module) For detailed information on the product description, see the Operating Instructions for the device Endress+Hauser...
Excessive tightening torque applied to the fixing screws! Risk of damaging the plastic transmitter. ‣ Tighten the fixing screws as per the tightening torque: 2 Nm (1.5 lbf ft) ø 20…70 TX 25 ø ( 0.79…2.75) SW 10 A0029051 1 Engineering unit mm (in) Endress+Hauser...
Mounting the transmitter housing: – Post mounting – Wall mounting Is the device undamaged (visual inspection)? Post mounting: Have the fixing screws been tightened with the correct tightening torque? Wall mounting: Are the securing screws tightened securely? Endress+Hauser...
Cable diameter • Cable glands supplied: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) • Spring-loaded terminals: Suitable for strands and strands with ferrules. Conductor cross-section 0.2 to 2.5 mm (24 to 12 AWG). Endress+Hauser...
Page 14
Current output 0/4 to 20 mA Standard installation cable is sufficient. Pulse/frequency/switch output Standard installation cable is sufficient. Relay output Standard installation cable is sufficient. Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Endress+Hauser...
Page 15
Maximum 26 µH IIC, maximum 104 µH IIB Inductance/resistance ratio Maximum 8.9 µH/Ω IIC, maximum 35.6 µH/Ω IIB (e.g. in accordance with IEC (L/R) 60079-25) Loop resistance Power supply line (+, –): maximum 5 Ω Cable length Maximum 150 m (500 ft), see the following table. Endress+Hauser...
Page 16
• A, B = 0.5 mm 5.1.4 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover. Endress+Hauser...
Page 17
Remove dummy plug if present. If the measuring device is supplied without cable glands: Provide suitable cable gland for corresponding connecting cable. If the measuring device is supplied with cable glands: Observe requirements for connecting cables → 13. Endress+Hauser...
Cable entry for cable on transmitter housing Protective earth (PE) Connecting cable ISEM communication Grounding via ground connection; on device plug versions grounding is through the plug itself Cable entry for cable or connection of device plug on sensor connection housing Protective earth (PE) Endress+Hauser...
Page 19
Option C "Ultra-compact hygienic, stainless" → 22 • Promass A, E, F, H, I, O, P, Q, S • CubemassC Connecting the connecting cable to the transmitter The cable is connected to the transmitter via terminals → 23. Endress+Hauser...
Page 20
Housing degree of protection voided due to insufficient sealing of the housing. ‣ Screw in the thread on the cover without using any lubricant. The thread on the cover is coated with a dry lubricant. Screw on the housing cover. Tighten the securing clamp of the housing cover. Endress+Hauser...
Page 21
Connect the cable in accordance with the connecting cable terminal assignment → 18. Firmly tighten the cable glands. This concludes the process for connecting the connecting cable. Close the housing cover. Tighten the securing screw of the housing cover. Endress+Hauser...
Page 22
Electrical connection Proline 500 – digital PROFIBUS DP Connecting the sensor connection housing via the connector A0029615 Connect the protective ground. Connect the connector. Endress+Hauser...
Page 23
This concludes the process for connecting the connecting cable. Close the housing cover. 10. Tighten the securing screw of the housing cover. 11. After connecting the connecting cable: Connect the signal cable and the supply voltage cable → 24. Endress+Hauser...
Page 24
Terminal connection for signal transmission, input/output; optional: connection for external WLAN antenna Protective earth (PE) TX 20 TX 20 10 (0.4) 22 mm 24 mm A0029597 Loosen the 4 fixing screws on the housing cover. Open the housing cover. Fold open the terminal cover. Endress+Hauser...
1 and 126. In a PROFIBUS DP/PA network, each address can only be assigned once. If an address is not configured correctly, the device is not recognized by the master. All measuring devices are delivered from the factory with the device address 126 and with the software addressing method. Endress+Hauser...
Page 26
Set the desired device address using the DIP switches. To switch addressing from software addressing to hardware addressing: set the DIP switch to On. The change of device address takes effect after 10 seconds. The device is restarted. Endress+Hauser...
Page 27
It is generally advisable to use an external bus terminator as the entire segment can fail if a device that is terminated internally is defective. A0029675 Open the housing cover. Remove the display module. Fold open the terminal cover. Endress+Hauser...
No special measures for potential equalization are required. For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA). Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. Endress+Hauser...
Are cables or the device undamaged (visual inspection)? Do the cables used meet the requirements? Do the cables have adequate strain relief? Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap" → 28? Endress+Hauser...
Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Field Xpert SMT70 Mobile handheld terminal Control system (e.g. PLC) Endress+Hauser...
The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. For detailed information on the operating philosophy, see the Operating Instructions for the device. Endress+Hauser...
2.6 Explanatory symbols for measured value 2: measured value type, measuring channel number Navigation view: picklist of a parameter 3.1 Navigation path and status area 3.2 Display area for navigation: designates the current parameter value Editing view: text editor with input mask Editing view: numeric editor with input mask Endress+Hauser...
Page 33
Moves the input position one position to the left. Switches to the selection of the correction tools. Deletes one character immediately to the left of the input position. Toggle • Between upper-case and lower-case letters • For entering numbers • For entering special characters Endress+Hauser...
Page 34
• Pressing the key for 2 s in the case of a parameter: Returns you to the operational display ("home position"). With a wizard: Exits the wizard and takes you to the next higher level. With a text and numeric editor: Closes the editor view without applying any changes. Endress+Hauser...
– Operating tools • Device master file (GSD) – Manufacturer-specific GSD – Profile GSD • Compatibility with previous model • Using the GSD modules of the previous model • Cyclic data transmission – Block model – Description of the modules Endress+Hauser...
Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1 Sprache Deutsch Betrieb Setup A0029420 4 Taking the example of the local display Endress+Hauser...
Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. The message about remedial measures can be called up from the diagnostic message, and contains important information on the fault. Endress+Hauser...
Page 38
The Diagnostic list submenu opens. Select the desired diagnostic event with or and press . The message about the remedial measures opens. Press + simultaneously. The message about the remedial measures closes. Endress+Hauser...