Toshiba W7 DN-57442-006 Installation & Operation Manual page 71

Adjustable speed drives
Table of Contents

Advertisement

ST Signal Selection
Program  Terminal  Input Special Functions
This parameter is used to set the operation of the Standby (ST) control
terminal or any terminal configured as the ST terminal.
Settings:
0 — Standard
1 — Always On
2 — Interlock with F/R Terminal
The setting ST-to-CC Required enables the ASD for operation so long as
the control terminal ST is connected to CC via a jumper, contact, or
other means.
The ST-to-CC Not Required setting allows the ASD to operate without
the ST-to-CC connection. The control terminal ST may be configured for
other functions.
The Interlock with F/R Terminal setting configures the F (Forward) and R
(Reverse) control terminals for the secondary function of Standby.
Closing a set of contacts to either F or R will cause the ASD to
accelerate the motor to the programmed setpoint of F or R. Opening the
F and R contact will disable the ASD and the motor will coast to a stop.
The control terminal ST may be configured for other functions.
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F103
Parameter Type — Selection List
Factory Default — Standard
Changeable During Run — No
F103-F103
61

Advertisement