Some alarm signals can be delayed with respect to the activation of a component to allow stable operating
conditions to be reached – for example:
Alarm A:FL (airflow absent or presence of fire-smoke) is not read during the first 30 seconds after fan start; this
value is linked to the FACTORY P1 parameter.
Alarms LO:C1 and LO:C2 (1/2 circuit low pressure) are not read during the first 180 seconds after start-up of
the relevant compressor. This value is linked to the FACTORY parameter P3.
ALAR
A
LARM
PA
Delay of low/high temperature/humidity alarm at start-up.
This establishes the delay in recognising low/high temperature and humidity
alarms at UNIT start-up. N.B.: The low humidity alarm is delayed at humidifier
start-up. This is to avoid a low humidity alarm when a possible humidifier
alarm is reset.
PC
General alarm delay. This establishes the activation delay of the ID5 general
alarm.
This establishes the delay in recognising the flow alarm from start of fan.
P1
P2
This establishes the delay in recognising the flow alarm while the fan is
operating.
This establishes the delay in recognising the low pressure alarm at
P3
compressor start-up to allow reaching a stable situation.
Two different types of alarm warnings are available: "serious " and "non-serious" alarms (see section
"DESCRIPTION OF ALARM CODES ").
In a configuration with more than one unit connected, serious alarms trigger the activation of the DO7 relay and
therefore the activation of the unit in stand-by.
In a configuration with no unit rotation, the FACTORY parameters HA and HF can be changed, in such a way as to
have two different alarm signals:
- "serious alarms" through the general alarm relay DO6;
- "non-serious alarms" through the dehumidification relay DO7 (CW/S and DX/S only).
GLb
G
ENERAL
HA
Configuration of digital output DO7:
2 = alarm relay for not critical alarms (follows the logic
set through the parameter HF)
3 = output for rotation control
HF
Alarm relay logic:
0 = de-energise in alarm for all the alarms
2 = de-energise in alarm only for the serious alarms
When an alarm occurs, the control performs the following actions:
displays the
de-energize the DO6 relay (general alarm); the relays functioning logic, normally energised
or de-energised, and the alarm category that activates this relay is set by the HF parameter
(default equals 0);
(in JUPITER CW/S and DX/S units, if HA is set to 2) relay D07 de-energised (non-serious alarm); relay
logic, normally energised or de-energised, is defined by parameter HF (default setting is 0);
lights up the red light of key
activates the buzzer (if the USER P4 parameter is set at a value other than zero).
mP30-UG30 - Rev. 1.5 - Date: 18-03-2004

DELAYS DUE TO ALARM SIGNALS

SERIOUS ALARMS

ACTIVE ALARMS

symbol and the alarm code;
;
EN
INSTRUCTION MANUAL
Minimu
Maximum
m
0
150
0
250
0
250
0
90
0
250
Min
Max
Default
0
3
3
0
3
0
Measurement
Default
unit
min
15
sec
0
sec
30
sec
3
sec
180
Setting to manage 2
alarms
2
2
37 (44)