Standard Maintenance; Level 1 Maintenance (See Note); Level 2 Maintenance (See Note); Level 3 (Or Higher) Maintenance (See Note) - Carrier Aqua Force 30XA Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

12 - sTaNDaRD MaINTENaNCE

Air conditioning equipment must be maintained by profes-
sional technicians, whilst routine checks can be carried out
locally by specialised technicians.
Simple preventive maintenance will allow you to get the
best performance from your HVAC unit:
improved cooling performance
reduced power consumption
prevention of accidental component failure
prevention of major time-consuming and costly inter-
ventions
protection of the environment
There are five maintenance levels for HVAC units, as
defined by the AFNOR X60-010 standard.

12.1 - level 1 maintenance (see note)

Simple procedure can be carried out by the user:
Visual inspection for oil traces (sign of a refrigerant
leak)
Air heat exchanger (condenser) cleaning - see chapter
"Condenser coil - level 1"
Check for removed protection devices, and badly
closed doors/covers
Check the unit alarm report when the unit does not
work (see report in the 30XA Pro-Dialog Plus control
manual).
General visual inspection for any signs of deterioration.

12.2 - level 2 maintenance (see note)

This level requires specific know-how in the electrical,
hydronic and mechanical fields. It is possible that these
skills are avail-able locally: existence of a maintenance
service, industrial site, specialised subcontractor.
In these cases, the following maintenance operations are
recommended.
Carry out all level 1 operations, then:
At least once a year tighten the power circuit electrical
connections (see tightening torques table).
Check and re-tighten all control/command connections,
if required (see tightening torques table).
Check the differential switches for correct operation
every 6 months (free-cooling option 118A).
Remove the dust and clean the interior of the control
boxes, if required.
Check the presence and the condition of the electrical
protection devices.
Check the correct operation of all heaters.
Replace the fuses every 3 years or every 15000 hours
(age-hardening).
Replace the control box cooling fans used with option
22 (with designation EF22_) every five years.
Check the height of the anti-vibration mountings
(located between the compressor rails and the unit
chassis) after 5 years of operation, and then each year.
When the total minimum height of the mountings is
less than 28 mm replace the mountings.
42
Check the water connections
Purge the water circuit (see chapter "Water flow control
procedure")
Clean the water filter (see chapter "Water flow control
procedure")
Fully clean the condensers with a low-pressure jet and
a bio-degradable cleaner (counter-current cleaning -
see chapter "Condenser coil - level 2)
Replace the stuffing box packing of the pump after
10000 hours of operation
Check the unit operating parameters and compare
them with previous values
Keep and maintain a maintenance sheet, attached to
each HVAC unit
All these operations require strict observation of adequate
safety measures: individual protection garments, compliance
with all industry regulations, compliance with applicable
local regulations and using common sense.

12.3 - level 3 (or higher) maintenance (see note)

The maintenance at this level requires specific skills/
approval/tools and know-how and only the manufacturer,
his representative or authorised agent are permitted to
carry out these operations. These maintenance operations
concern for example:
A major component replacement (compressor, evapo-
rator)
Any intervention on the refrigerant circuit (handling
refrigerant)
Changing of parameters set at the factory (application
change)
Removal or dismantling of the HVAC unit
Any intervention due to a missed established mainte-
nance operation
Any intervention covered by the warranty
NOTE: Any deviation or non-observation of these mainte-
nance criteria will render the guarantee conditions for the
HVAC unit nul and void, and the manufacturer, France,
will no longer be held responsible.
12.4 - Tightening torques for the main electrical
connections
Component
Screw on bus bar, customer connection
M8
M10
Soldered screw PE, customer connection (M12)
Tunnel terminal screw, compressor contactor
Contactor 3RT103*
Contactor 3RT104*
Contactor 3RT105*
Contactor 3RT106*
Tunnel terminal screw, current transformer
Size 2 (3RB2956*)
Size 3 (3RB2966*)
Compressor earth terminal in the power wiring
control box, terminal M8
Compresor phase connection terminals M12
Compressor earth connection
Tunnel terminal screw, disconnects 3RV1011*
Tunnel terminal screw, hydronic pump contactor
Contactor 3RT101*
Contactor 3RT102*
Screw on bus bar for power connection between
the control boxes for option 81
Designation
Value
in the unit
(Nm)
18
L1/L2/L3
30
PE
70
5
11
KM*
21
11
TI*
21
Gnd
30
1/2/3/4/5/6 on EC
25
Gnd on EC*
25
QF*/QM*
1
KM90*
1
2.2
L1/L2/L3
30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents