Free-Cooling Option; Characteristics; Operating Limits; Operation - Carrier Aqua Force 30XA Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

8 - fREE-COOlING OPTION

8.1 - Characteristics

30Xa with Option 118a
Operating weight*
Refrigerant charge
Circuit A
Circuit B
Refrigerant charge, option 254
Circuit A
Circuit B
*
Standard unit and option 119
**
Option 118A (free cooling) is not compatible with these units.

8.2 - Operating limits

Cooling mode
Evaporator
Entering water temperature at start-up
Entering water temperature during operation
Leaving water temperature during operation
Condenser (air)
Outdoor ambient operating temperature
With winter operation option (option 28)
free-cooling mode
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation
Condenser (air)
Outdoor ambient operating temperature
With winter operation option (option 28)
*
Maximum configurable set-point

8.3 - Operation

7
5
8
4
9
6
3
2
legend
1
Evaporator
2
Air condenser (coils)
3
Motorised two-way valve, discharge side
4
Compressor and oil separator
5
Principal electronic expansion valve (EXV)
6
Pressure and temperature measurement to calculate the sub-cooling upstream
of the pump
7
Motorised two-way bypass valve
8
Free-cooling expansion device (EXV)
9
Refrigerant pump
252
302
352
kg
3840
3880
3920
kg
36
37
37
38
38
39
kg
60
64
**
64
64
**
Minimum
Maximum
°C
-
45
°C
6.8
21
°C
3.3
26
Minimum
Maximum
°C
-10
55*
°C
-20
55*
Minimum
Maximum
°C
-
45
°C
3,3
26*
Minimum
Maximum
°C
-10
20
°C
-20
20
1
7
5
8
9
6
2
402
452
502
602
4780
4850
5330
6260
54
56
64
64
37
39
39
64
87
87
104
104
56
56
56
90
The change-over between the cooling and free-cooling
modes is automatically controlled (it is possible to block the
change-over to free-cooling by reconfiguring the machine -
see Controls IOM). The configurable parameters permitting
change-over are the outside air temperature and the leaving
water temperature set-point. As soon as the temperature
difference LWTstp - OAT is above 8 K the current capacity
in cooling mode is calculated and compared with the theo-
retical free-cooling capacity. This comparison authorizes/
stops the change-over to free-cooling.
After change-over to free-cooling all compressors are
stopped, the two (or four) two-way valves change to the free-
cooling position (the compressor functions are bypassed).
As soon as the valves open, the free-cooling pump is started.
This change-over logic takes around 4 minutes. Taking this
timing into consideration two cooling - free-cooling change-
overs are authorized per hour.
If the capacity supplied in the free-cooling mode is insuffi-
cient (set-point not reached), the unit automatically changes
over to cooling mode.
To optimize operation in free-cooling mode we strongly
recommend to use the set-point offset function. This favours
the change-over to free-cooling and increases the capacity
in free-cooling mode.
4
3
702
752
802
852
6410
6710
7010
7560
64
72
76
79
68
64
67
70
102
**
**
133
97
**
**
97
902
1002
7860
8440
76
83
79
87
**
143
**
132
31