Split unit air conditioner
ceiling mounted c series; e series; fl-e series; fh-c series; fly-e series; fhy-c series
cooling only & heatpump [50hz] (78 pages)
Si01-782 Table of Contents 1. Removal of Outer Panels ................2 2. Removal of Fan Motor / Outdoor Fan .............5 3. Removal of Electrical Components ASSY ..........7 4. Removal of Sound Blankets..............11 5. Removal of Compressor ...............12 Note: The illustrations may be slightly different depending on the model. Removal Procedure...
Removal of Outer Panels Si01-782 1. Removal of Outer Panels Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the top panel. Top panel Remove the 8 screws of the top panel.
Page 5
Si01-782 Removal of Outer Panels Step Procedure Points Unfasten the hooks with a flat screwdriver and remove the suction Hook grille. (R5427) 2. Remove the front panel (2). Remove the screw and remove the front panel (2). Front panel (R12807) When reassembling, fit the 5 hooks.
Page 6
Removal of Outer Panels Si01-782 Step Procedure Points 4. Remove the front panel (1). Remove the 6 screws and remove the front panel (1). Front panel (1) (R12810) (R5432) (R8322) Removal Procedure...
Si01-782 Removal of Fan Motor / Outdoor Fan 2. Removal of Fan Motor / Outdoor Fan Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Disconnect the each wire Preparation Terminal Board harness.
Page 8
Removal of Fan Motor / Outdoor Fan Si01-782 Step Procedure Points 2. Remove the outdoor fan. Nut size : M8 Remove the nut and remove the outdoor fan. 13 mm (R12301) Lock washer When reassembling, fit the (R5438) D-cuts of the lock washer and the shaft of fan motor.
Si01-782 Removal of Electrical Components ASSY 3. Removal of Electrical Components ASSY Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the side panel. Preparation Remove the top panel, front Remove the 9 screws panel (1) (2), and piping...
Page 10
Removal of Electrical Components ASSY Si01-782 Step Procedure Points 2. Remove the outdoor temperature thermostat. Detach the outdoor temperature sensor. Outdoor temperature sensor Remove the sensor fixing plate. (R12813) (R12814) Disconnect the flag shape terminals of the outdoor air thermostat. Outdoor air thermostat (R6744)
Page 11
Si01-782 Removal of Electrical Components ASSY Step Procedure Points 3. Remove the capacitor. Disconnect the terminals from the capacitor. Capacitor (R6746) 4. Disconnect the each wire harness. Cut the clamp. (R6747) Disconnect the blue terminal. Blue (R6748) Detach the clamp for the compressor lead wire (rear side).
Page 12
Removal of Electrical Components ASSY Si01-782 Step Procedure Points 5. Remove the electrical components ASSY. Lift the electrical Electrical components ASSY components ASSY to unfasten the 2 hooks and remove it. (R6750) Removal Procedure...
Si01-782 Removal of Sound Blankets 4. Removal of Sound Blankets Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the sound Preparation blanket (top). Remove the electrical box according to the "Removal of Electrical Components ASSY".
Removal of Compressor Si01-782 5. Removal of Compressor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the terminal cover. Terminal cover (R5455) Terminal cover fixture (R5456) Disconnect the Be careful so as not to burn...
Page 15
Si01-782 Removal of Compressor Step Procedure Points Remove the 4 nuts of the compressor. Warning Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas brazing machine. Warning Before working, make If the refrigerant gas leaks sure that the refrigerant is during work, ventilate the...
Page 16
Revision History Month / Year Version Revised contents 07 / 2013 Si01-782 First edition...
Page 17
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.