Bryant 580D Product Information Manual page 48

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons
Table of Contents

Advertisement

579F216 (18 TONS)*
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
5000
669
1.10
1019
5500
717
1.40
1292
6000
767
1.80
1617
6500
817
2.20
1992
7000
869
2.70
2427
7200
889
2.94
2624
7500
920
3.30
2919
8000
973
3.90
3476
8500
1026
4.60
4102
9000
1079
5.40
4800
579F216 (18 TONS)* (cont)
Airflow
1.3
(Cfm)
Rpm
Bhp
Watts
5000
1178
3.15
2820
5500
1196
3.55
3164
6000
1218
4.00
3565
6500
1244
4.50
4022
7000
1275
5.05
4547
7200
1288
5.33
4783
7500
1307
5.75
5135
8000
8500
9000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Standard low-medium static drive range is 817 to 1038 rpm. Alternate
high static high static motor drive range is 994 to 1197. Other rpms re-
quire a field-supplied drive.
NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-
nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.
PERFORMANCE DATA (cont)
FAN PERFORMANCE — 579F180-300 UNITS (cont)
External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
Bhp
772
1.40
1291
870
1.80
813
1.80
1585
905
2.10
858
2.20
1932
944
2.50
903
2.60
2329
985
3.00
950
3.10
2787
1028
3.50
969
3.34
2993
1046
3.74
998
3.70
3303
1073
4.10
1047
4.30
3886
1119
4.80
1097
5.10
4635
1166
5.60
External Static Pressure (in. wg)
1.4
Rpm
Bhp
Watts
Rpm
1218
3.40
3016
1295
1234
3.80
3366
1309
1251
4.20
3772
1327
1279
4.70
4233
1348
1308
5.30
4762
0.6
0.8
Watts
Rpm
Bhp
Watts
1582
963
2.10
1903
1892
992
2.50
2223
2256
1026
2.90
2600
2673
1062
3.40
3031
3151
1102
3.90
3527
3366
1118
4.18
3749
3689
1143
4.60
4083
4294
1186
5.30
4708
4967
1.6
1.8
Bhp
Watts
Rpm
Bhp
Watts
3.80
3425
1369
4.30
4.20
3789
1381
4.70
4.70
4206
1396
5.20
5.20
4677
1415
5.80
2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 5.9 and the maximum continuous watts
are 5180. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized with con-
fidence. Using your fan motors up to the watts rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
4. Deduct 0.2 in. wg static pressure for high heat units at or above
8000 cfm.
48
1.0
Rpm
Bhp
Watts
Rpm
1052
2.50
2251
1137
1076
2.90
2680
1157
1104
3.30
2967
1181
1136
3.80
3410
1209
1172
4.40
3919
1241
1187
4.64
4147
1255
1210
5.00
4490
1275
1250
5.70
5131
3849
4229
4658
5139
1.2
Bhp
Watts
2.90
2623
3.30
2962
3.80
3358
4.30
3811
4.80
4331
5.08
4564
5.50
4914