Bryant 580D Product Information Manual page 54

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons
Table of Contents

Advertisement

ALTITUDE COMPENSATION* — 580D090-150
125,000, 180,000,
AND 224,000 BTUH
NOMINAL INPUT
ELEVATION
Natural
(ft)
Gas
Orifice
Size†
0-2,000
31
2,000
32
3,000
32
4,000
32
5,000
33
6,000
34
7,000
35
8,000
36
9,000
37
10,000
38
11,000
39
12,000
40
13,000
41
14,000
42
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes.
†Orifices available through your local distributor.
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT
580D036,048
580D060
580D072
580D090-120
580D150
579F180 (3.7 Hp)
579F216 (5 Hp)
579F240 (7.5 Hp)
579F300 (10 Hp)
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
Fan Performance Using Accessory Power Exhaust (579F180-300)
PERFORMANCE DATA (cont)
250,000 BTUH
NOMINAL INPUT
Liquid
Natural
Liquid
Propane
Gas
Propane
Orifice
Orifice
Orifice
Size†
Size†
Size†
41
30
38
42
30
39
42
31
40
42
32
41
43
33
42
43
34
43
44
35
43
44
36
44
45
37
44
46
38
45
47
39
45
47
40
46
48
41
47
48
42
47
MOTOR EFFICIENCY (%)
75
74
84
80
87
85.8
87.5
88.5
89.5
ALTITUDE COMPENSATION* —
ELEVATION
(ft)
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher
altitudes.
†Orifices available through your local distributor.
ALTITUDE DERATING FACTOR* —
ELEVATION
(ft)
0-2,000
2,001-3,000
3,001-4,000
4,001-5,000
5,001-6,000
*Derating of the unit is not required unless the heating value of the gas
exceeds the values listed in the table above, or if the elevation exceeds
6000 ft. Derating conditions must be 4% per thousand ft above sea
level. For example, at 4000 ft, if the heating value of the gas exceeds
3
1000 Btu/ft
, the unit will require a 16% derating. For elevations above
6000 ft, the same formula applies. For example, at 7000 ft, the unit will
require a 28% derating of the maximum heating value per the National
Fuel Gas Code.
54
579F180-300
NATURAL GAS ORIFICE SIZE†
Lo Heat
High Heat
28
29
29
29
29
30
29
30
30
30
30
30
31
31
31
31
31
31
32
32
ALL UNITS
MAXIMUM HEATING VALUE
3
(Btu/ft
)
1,100
1,050
1,000
950
900