Bryant 580D Product Information Manual page 49

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons
Table of Contents

Advertisement

579F240 (20 TONS)*
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
6000
767
1.80
1617
6500
817
2.20
1992
7000
869
2.70
2427
7500
920
3.30
2919
8000
973
3.90
3476
8500
1026
4.60
4102
9000
1079
5.40
4800
9500
1133
6.20
5576
10,000
1188
7.20
6432
579F240 (20 TONS)* (cont)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
6000
1255
4.20
3772
6500
1279
4.70
4233
7000
1308
5.30
4762
7500
1339
6.00
5356
8000
1373
6.70
6024
8500
1410
7.60
6765
9000
1449
8.50
7584
9500
1488
9.40
8403
10,000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Standard low-medium static motor drive range is 1002 to 1225 rpm. Al-
ternate high static motor drive range is 1193 to 1458 rpm. Other rpms
require a field-supplied drive.
NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-
nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.
PERFORMANCE DATA (cont)
FAN PERFORMANCE — 579F180-300 UNITS (cont)
External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
Bhp
858
2.20
1932
944
2.50
903
2.60
2329
985
3.00
950
3.10
2787
1028
3.50
998
3.70
3303
1073
4.10
1047
4.30
3886
1119
4.80
1097
5.10
4635
1166
5.60
1147
5.90
5257
1214
6.40
1199
6.80
6058
1263
7.30
1250
7.80
6939
1313
8.30
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
Bhp
1327
4.70
4206
1396
5.20
1348
5.20
4677
1415
5.80
1373
5.80
5215
1437
6.40
1401
6.50
5818
1462
7.00
1433
7.30
6495
1493
7.80
1467
8.10
7248
1524
8.70
1503
9.00
8033
0.6
0.8
Watts
Rpm
Bhp
Watts
2256
1026
2.90
2600
2673
1062
3.40
3031
3151
1102
3.90
3527
3689
1143
4.60
4083
4294
1186
5.30
4708
4967
1231
6.00
5401
5714
1276
6.90
6171
6540
1323
7.90
7018
7444
1371
8.90
7946
1.8
1.9
Watts
Rpm
Bhp
Watts
4658
1431
5.45
4884
5139
1449
6.10
5370
5686
1469
6.70
5922
6298
1493
7.25
6538
6966
1523
8.05
7202
7731
2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 8.7 for 208/230-v units and 9.5 for 460-v
units. The maximum continuous watts are 7915 for the 208/230-v
units and 8640 for the 460-v units. Extensive motor and drive testing
on these units ensures that the full horsepower range of the motor
can be utilized with confidence. Using your fan motors up to the
watts rating shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
4. Deduct 0.2 in. wg static pressure for high heat units at or above
9000 cfm. Deduct 0.3 in. wg static pressure for high heat units at or
above 10,000 cfm.
49
1.0
Rpm
Bhp
Watts
Rpm
1104
3.30
2967
1181
1136
3.80
3410
1209
1172
4.40
3919
1241
1210
5.00
4490
1275
1250
5.70
5131
1313
1292
6.50
5843
1352
1336
7.40
6632
1393
1381
8.40
7500
1436
1426
9.50
8449
2.0
Rpm
Bhp
Watts
1465
5.70
5110
1482
6.40
5601
1501
7.00
6157
1523
7.50
6778
1.2
Bhp
Watts
3.80
3358
4.30
3811
4.80
4331
5.50
4914
6.20
5569
7.00
6297
7.90
7102
8.90
7988