Bryant AIR CONDITIONER WITH PURONR 113A Product Data page 22

Legacy-rnc series air conditioner with puron
Hide thumbs Also See for AIR CONDITIONER WITH PURONR 113A:
Table of Contents

Advertisement

GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor- -mounted, air- -cooled, split- -system air conditioner
unit suitable for ground or rooftop installation. Unit consists
of a hermetic compressor, an air- -cooled coil, propeller- -type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil
or coil unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of ARI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval.
Unit will have c- -UL approval.
— Unit cabinet will be capable of withstanding Federal
Test
Method Standard No. 141 (Method 6061) 500- -hr salt
spray test.
— Air- -cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is
stored
and
recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air- -cooled air conditioner
unit. Contained within the unit enclosure is all factory wiring,
piping, controls, compressor, refrigerant charge Puronr
(R- -410A), and special features required prior to field start- -up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
handled
per
unit
manufacturer's
AIR- -COOLED, SPLIT- -SYSTEM AIR CONDITIONER
Fans
— Condenser fan will be direct- -drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed,
1- -phase type with class B insulation and permanently
lubricated bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically
balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil
mechanically bonded to copper tubes which are then
cleaned, dehydrated, and sealed.
Refrigeration Components
— Refrigeration
liquid- -line shutoff valve with sweat connections,
vapor- -line shutoff valve with sweat connections,
system charge of Puronr (R- -410A) refrigerant, and
compressor oil.
— Unit will be equipped with high- -pressure switch, low
pressure switch and filter drier for Puron refrigerant.
Operating Characteristics
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F. The power
consumption at full load will not exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F wet bulb
and _____ _F dry bulb, and air entering the unit at
_____ _F.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying
accessories and descriptions for specific features and
available enhancements.
Printed in U.S.A.
Edition Date: 12/05
22
1- -1/2 TO 5 NOMINAL TONS
will
be
constructed
of
circuit
components
Catalog No. PDS 113A.18.1
Replaces: NEW
113A
aluminum
fins
will
include

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents