Table of Contents

Advertisement

3. Insulate and caulk wall openings to reduce air infil-
tration and refrigerant pipe vibrations on structure.
4. Evacuate piping, if necessary. If either refrigerant
piping or the indoor coil is exposed to atmospheric
conditions, it must be evacuated to 1000 microns to
eliminate contamination and moisture in the system.
V. STEP 5 — CONNECT CONDENSATE DRAIN LINE
Observe all local sanitary codes when installing condensate
drains. Refer to Fig. 3 and 14 for drain pipe connection from
indoor unit.
1. Use hard polyvinyl chloride (PVC) pipe material with
3
nominal ID of
/
in. to connect at drain line. Use pipe
4
1
insulation
/
-in. thick, such as Armaflex insulation,
4
on exposed piping inside the conditioned space.
2. To ensure regular flow of condensate water, the drain
pipe should be pitched toward an open drain or sump
at a downward slope of at least
HEAT PUMP
INDOOR UNIT SIZE
024
036
048
060
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
Table 4C — Piston and Charge Combinations — Heat and Cool Systems
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
1
/
-in. per ft.
4
Table 4A — Piston and Charge Combinations — Cooling Only Systems
COOLING
OUTDOOR UNIT
INDOOR UNIT SIZE
024
036
048
060
Table 4B — Piston and Charge Combinations — Heat Pump Systems
OUTDOOR UNIT
538B
018
024
030
036
048
060
HEAT PUMP
OUTDOOR UNIT
INDOOR UNIT SIZE
024
036
048
060
3. Attach plate with screws under piping hole.
4. Attach drain pipe with nylon wire tie passing through
hole (Fig. 15).
NOTE: Do not fasten nylon wire ties tight enough to
deform the insulation, as this affects its performance.
5. Insulate condensate drain line(s) that are located in
or above an occupied area with a condensate-proof
material such as polyurethane or neoprene.
6. Install an external trap at the end of the condensate
line.
NOTE: Should the installation require one, a
condensate pump may be ordered as a field-installed
accessory.
PISTON
538A
SIZE
018
57
024
57
030
65
036
70
048
80
060
90
PISTON SIZE
PISTON SIZE
INDOOR
OUTDOOR
49
55
65
70
82
—*
PISTON
538A
SIZE
018
57
024
57
030
65
036
70
048
80
060
—*
—8—
CHARGE (lb)
7.0
7.75
10.1
8.9
12.2
12.5
CHARGE (lb)
40
7.5
43
7.8
55
12
63
13
73
12.2
80
12.8
CHARGE (lb)
7.0
7.75
10.1
8.9
12.2
12.5