Step 10 — Install External Condensate Trap & Line
3
The unit has one
/
-in. condensate drain connection on the
4
end of the condensate pan (see Fig. 21). See Figs. 2, 3 and
4, item "E", in the view labeled "BACK" for the location of
the condensate drain connection.
STANDARD
SIDE DRAIN
Fig. 21 - - Condensate Drain Pan Connection
The piping for the condensate drain and external trap can
be completed after the unit is in place. Hand tighten
fittings to the drain pan fitting. Provide adequate support
for the drain line. Failure to do so can result in damage to
the drain pan. See Fig. 22.
MINIMUM PITCH
1" (25mm) PER
BASE RAIL
10' (3m) OF LINE
OPEN
VENT
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4" (102mm) trap is recommended
Fig. 22 - - Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
3
(
/
-in.).
4
C09056
3˝ (76mm)
MIN
SEE NOTE
ROOF
CURB
DRAIN PLUG
C11291
Step 11 — Make Electrical Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
NOTE:
Field- - supplied wiring shall conform with the
limitations of minimum 63_F (33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet's
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always- - energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit- - mounted
disconnect. (Check with local codes to ensure this method
is acceptable in your area.) On a unit without a
unit- - mounted disconnect, connect the source leads to the
terminal block with unit field power leads. See Fig. 23.
BLK
YEL
BLU
LOAD
SIDE
LINE
SIDE
SEE
DETAIL
L1
L2
L3
A
DETAIL
Fig. 23 - - Location of TB1
Field power wires are connected to the unit at line- - side
pressure lugs on the terminal block (see wiring diagram
label for control box component arrangement) or at
factory- - installed option non- - fused disconnect switch. Use
copper conductors only.
NOTE: Make field power connections directly to line
connection pressure lugs only.