8-2
ELECTRICAL CHARACTERISTICS
Units
Model
Hz Volts
FXKQ25 · 32M(A)VE(9)
220-
FXKQ40M(A)VE(9)
50
240
FXKQ63M(A)VE(9)
FXKQ25 · 32M(A)VE(9)
FXKQ40M(A)VE(9)
60
220
FXKQ63M(A)VE(9)
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
8-3
SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
Power supply wiring
Model
Field
fuses
Wire
FXKQ25 ·
32M(A)VE(9)
H05V
15A
V-U3G
FXKQ40M(A)VE(9)
NOTE 1)
FXKQ63M(A)VE(9)
Allowable length of transmission wiring between indoor/outdoor
units and between the indoor unit and the remote controller is as
follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
NOTE
1. Shows only in case of protected piping. Use H07RN-F in
case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1mm
or more)
9.
WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
9-1
HOW TO CONNECT WIRINGS
• Refer to the figure below when connecting the remote control-
ler wiring with transmission wiring and power supply wiring.
Wire clip
Electric parts box
Attached
clamp
Ground terminal
Remote
controller wiring
and Transmission
wiring between units (*)
Rubber bush
Terminal block for
remote controller (6P)
(NOTE 2)
8
Power
Fan motor
supply
Voltage
MCA MFA
kW
FLA
range
0.3
15
0.015 0.2
Max. 264
0.3
15
0.020 0.2
Min. 198
0.5
15
0.045 0.4
0.4
15
0.015 0.3
Max. 242
0.5
15
0.020 0.4
Min. 198
0.6
15
0.045 0.5
Remote controller
wiring
Transmission wiring
Size
Wire
Size
Wiring size
0.75
Sheathed
and length
wire
must com-
1.25
(2 wire)
ply with
NOTE 2)
mm
local codes.
Power supply
terminal block (2P)
(NOTE 1)
Power
supply
wiring and
ground
wiring (*)
Plastic
clamp
Electric parts
box lid
NOTE 1: Details of terminal block for power supply
Plastic clamp
NOTE 2: Details of terminal block for unit
transmission wirings
Remote controller wiring (*)
(Field wiring)
Clamp
(accessory)
-
• You can temporarily hang the electric parts box of the unit
from the position shown in the figure below. Use according to
2
the type of work.
CAUTION
• Be sure to attach the sealing material or putty (field supplied)
to hole of wiring to prevent the infiltration of water as well as
any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure
the lid on the electric parts box lid fits snugly by arranging the
wires neatly and attaching the electric parts box lid firmly.
When attaching the electric parts box lid, make sure no wires
get caught in the edges. Pass wiring through the wiring
through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through the
same locations outside of the unit, separating them by at
least 50mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.
Electric parts box
Power supply wiring
and ground wiring (*)
(Field wiring)
Transmission wiring
between units (*)
(Field wiring)
T2 T1 F2 F1 P2 P1
Electric parts box
English

Hide quick links: