• Attach a canvas duct each to the air outlet and air inlet so that
the vibration of the equipment will not be transmitted to the
duct or ceiling.Use a sound absorbing material (insulation
material) for the lining of the duct and apply vibration
insulation rubber to the hanging bolts.
At the time of duct welding, perform the curing of the duct so
that the spatter will not come in contact with the drain pan for
the filter.
If the metal duct pass through a metal lath, wire lath, or metal
plate of a wooden structure, separate the duct and wall elec-
trically.
Be sure to heat insulate the duct for the prevention of dew
condensation. (Material: Glass wool or styrene foam; Thick-
ness: 25 mm)
Explain the operation and washing methods of the locally
procured components (i.e., the air filter, air inlet grille, and air
outlet grille) to the customer.
Locate the air outlet grille on the indoor side for the preven-
tion of drafts in a position where indirect contact with people.
The air conditioner incorporates a function to adjust the fan to
rated speed automatically. (11. FIELD SETTING)
Therefore, do not use booster fans midway in the duct.
Connection method of ducts on air inlet and outlet sid es.
• Connect the field supply duct in alignment with the inner side
of the flange.
• Connect the flange and unit with the flange connection screw
(field supply).
• Wrap aluminum tape around the flange and duct joint in order
to prevent air leakage.
Flange on air inlet side
(provided with the unit)
Screws for duct
flanges
(field supply)
Air inlet
Insulation material
(field supply)
!
CAUTION
Connect the flange and unit with the flange connection screw
(Field supply) regardless of whether the duct is connected to the
air inlet side.

9. ELECTRIC WIRING WORK

9-
GENERAL INSTRUCTIONS
1
Shut off the power before starting any work.
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also "Wiring diagram"
attached to the el. compo. box lid.
• For remote controller wiring details, refer to the installation
manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal board
wiring to the outdoor unit and BS unit are properly matched.
If wiring and piping between the outdoor unit and an indoor
unit are mismatched, the system may cause a malfunction.
A circuit breaker capable of shutting down power supply to
the entire system must be installed.
Flange on air outlet side
(provided with the unit)
Insulation material
(field supply)
Screws
Air outlet
Unit
for duct
flanges
Canvas duct
(field supply)
(field supply)
• Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes,
lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods : might cause
abnormally high electric potential in the ground during
lighting storms.
9-
ELECTRIC CHARACTERISTICS
2
Units
Model
Volts
Hz
40 TYPE
50 TYPE
63 TYPE
50
230
80 TYPE
100 TYPE
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
9-
SPECIFICATIONS FOR FIELD SUPPLIED
3
FUSES AND WIRE
Power supply wiring
Model
Field fuses
40 TYPE
15A
50 TYPE
15A
63 TYPE
15A
H05VV-U3G
80 TYPE
15A
100 TYPE
15A
Allowable length of transmission wirings and remote
controller wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller: Max. 500 m
NOTE
1.Shows only in case of protected pipes. Use H07RN-F in
case of no protection.
2.Vinyl cord with sheath or cable (Insulated thickness : 1mm or
more)
10.
WIRING EXAMPLE AND HOW TO
SET THE REMOTE CONTROLLER
10
HOW TO CONNECT WIRINGS
-
1
(Remove the control box lid
and wire as shown in the
figure below.)
(Remove the el. compo.
box lid as shown below
and connect each wire.)
(1) Remove the
el. compo. box lid.
Power supply
Fan motor
Voltage
MCA
MFA
kW
range
0.8
15
0.055
1.2
15
0.100
Max. 253
1.0
15
0.080
Min. 207
1.6
15
0.130
1.6
15
0.180
Remote controller wiring
Transmission wiring
Wire
Size
Wire
Size must
comply with
0.75-1.25 mm²
local codes.
Screw
(3 portions)
9
FLA
0.65
0.92
0.83
1.30
1.30