Specifications for field supplied fuses and wire
Model
Field fuses
50, 63
16 A
Model
Wire
50, 63
Sheathed wire (2)
NOTE
For details, refer to
Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:
1.
Outdoor unit - indoor unit: max. 1000 m (total wiring length:
2000 m)
2.
Indoor unit - remote controller: max 500 m
Wiring example and how to set the remote
controller
How to connect wiring
Remove the switch box cover as shown in
connections.
1
Switch box cover
2
Switch box low voltage wiring inlet
3
Switch box high voltage wiring inlet
4
Wiring diagram
5
Switch box
Precautions
1.
Observe the notes mentioned below when wiring to the power
supply terminal board.
Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
1
2
3
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
When connecting wires of the same gauge, connect them
according to the figure.
Use the specified electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. Use torques according to the table below.
Tightening torque (N•m)
Terminal block for remote controller
Terminal block for power supply
When attaching the control box lid, make sure not to pinch
any wires.
After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.
Power supply wiring
Wire
Size
H05VV-U3G
Local codes
Size
0.75-1.25 mm
"Wiring example" on page
8.
figure
12, and make the
1
Round crimp-style terminal
2
Attach insulation sleeve
3
Wiring
0.79~0.97
1.18~1.44
2.
Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
3.
Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.
4.
For the remote controller wiring, refer to the "Installation manual
2
of the remote controller" supplied with the remote controller.
The customer has the ability to select the remote
NOTE
controller thermistor.
5.
Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.
6.
Use only specified wires and tightly connect wires to the terminals.
Be careful that wires do not place external stress on the terminals.
Keep wiring in neat order so that they do not obstruct other
equipment such as popping open the switch box cover. Make sure
the cover closes tight. Incomplete connections could result in
overheating, and in the worse case, electric shock or fire.
Keep total current of crossover wiring between indoor units less than
12 A. Branch the line outside the terminal block of the unit in
accordance with the electrical equipment standards, when using two
power wiring of a gauge greater than 2 mm
The branch must be sheathed in order to provide an equal or greater
degree of insulation as power supply wiring itself.

Wiring example

Fit the power supply wiring of each unit with a switch and fuse as
shown in
figure
16.
1
Power supply
2
Main switch
3
Power supply wiring
4
Transmission wiring
5
Switch
6
Fuse
7
BS unit REYQ only
8
Indoor unit
9
Remote controller
Complete system example (3 systems)
When using 1 remote controller for 1 indoor unit (Normal operation)
(See figure 15)
For group control or use with 2 remote controllers
When including BS unit
1
Outdoor unit
2
Indoor unit
3
Remote controller (optional accessories)
4
Most downstream indoor unit
5
For use with 2 remote controllers
6
BS unit
NOTE
It is not necessary to designate an indoor unit address
when
automatically set when the power is activated.
2
(Ø1.6).
(See figure 17)
(See figure 13)
using
group
control.
The
address
is
8