U2-02-09-12 - Inverter Circuit Power Supply Abnormality - Inverter Pcb A3P Phase Loss; U2-03-10-13 - Inverter Circuit Power Supply Abnormality - Inverter Pcb A3P Dc Circuit Not Charging - Daikin VRV IV+ Service Manual

Table of Contents

Advertisement

2 Troubleshooting
Trigger
Effect
Inverter PCB A3P
Unit will stop
detects DC voltage
operating.
cannot reach or
maintain minimum
500 V DC.
No zero cross is
detected by main
PCB through at least
10 seconds.
Abnormal voltage
drop is detected by
DC voltage detection
circuit.
Abnormal voltage rise
is detected by over
voltage detection
circuit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Check if the power supply wiring is correct. See
circuit" on
page 130.
Possible cause: Incorrect power supply wiring.
2 Perform a check of the noise filter PCB A2P. See
filter PCB" on
page 110.
Possible cause: Faulty noise filter PCB A2P.
3 Perform a check of the inverter PCB A3P. See
PCB" on
page 99.
Possible cause: Faulty inverter PCB A3P.
4 Check the wiring between the PCB's. See
diagram" on
page 146.
Possible cause: Faulty wiring between PCB's.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
2.3.115 U2-02-09-12 – Inverter circuit power
supply abnormality - inverter PCB A3P
phase loss
Main error code
Sub error code
U2
02
09
12
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple
outdoor unit configurations. Main outdoor unit is the unit to
which F1‑F2 IN transmission line is connected. Main, Sub
1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Service manual
54
https://daikin-p.ru/catalog/vrv-daikn/naruzhnye-vrv-bloki-daikin
Reset
Power reset at
outdoor unit.
"4.1 Electrical
"3.10  Noise
"3.8  Inverter
"6.2  Wiring
Unit
Main
Sub 1
Sub 2
Trigger
Effect
Inverter PCB A3P
Unit will stop
detects DC voltage
operating.
cannot reach or
maintain minimum
500 V DC.
No zero cross is
detected by main
PCB through at least
10 seconds.
Abnormal voltage
drop is detected by
DC voltage detection
circuit.
Abnormal voltage rise
is detected by over
voltage detection
circuit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1 Check if the power supply wiring is correct. See
circuit" on
page 130.
Possible cause: Incorrect power supply wiring.
2 Perform a check of the noise filter PCB A2P. See
filter PCB" on
page 110.
Possible cause: Faulty noise filter PCB A2P.
3 Perform a check of the inverter PCB A3P. See
PCB" on
page 99.
Possible cause: Faulty inverter PCB A3P.
4 Check the wiring between the PCB's. See
diagram" on
page 146.
Possible cause: Faulty wiring between PCB's.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
2.3.116 U2-03-10-13 – Inverter circuit power
supply abnormality - inverter PCB A3P DC
circuit not charging
Main error code
Sub error code
U2
03
10
13
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple
outdoor unit configurations. Main outdoor unit is the unit to
which F1‑F2 IN transmission line is connected. Main, Sub
1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Reset
Power reset at
outdoor unit.
"4.1 Electrical
"3.10  Noise
"3.8  Inverter
"6.2  Wiring
Unit
Main
Sub 1
Sub 2
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ Heat Pump
ESIE18-14 – 2019.07