Position Loop Auto-Tuning - Omron CK3M-CPU 1 Series Application Manual

Programmable multi-axis controller
Hide thumbs Also See for CK3M-CPU 1 Series:
Table of Contents

Advertisement

3 Connection Procedures
2
Set the following tuning parameters.
Amplitude: 1.0%
Test Time: 1,000 ms
Repetitions: 2
*1. If the motor does not rotate, set a
larger value.
3
Click the Open Loop Step button.
The motor makes a reciprocating mo-
tion, and then the test results as
shown on the right are displayed.
If the motor does not rotate, increase
the Test Amplitude value.
Here, the test results when Test
Amplitude is set to 8.0% are shown.
3-4-6

Position Loop Auto-tuning

Perform the position loop auto-tuning in the linear motor.
1
Select Position Loop Auto-tune –
Simple tab page on the Tune screen.
3-30
*1
Application Guide Laser Application (O052)