Machines With A Fan; Machines Without A Fan (Optional) - Siemens SIMOTICS SD 1LE5 Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

3.3.3.1

Machines with a fan

Self-ventilation (standard): Cooling method IC 411 according to EN / IEC 60034-6
Located at the ND end of the stator housing is an air intake cowl that guides the external air
on its way to the motor. The external air is drawn in through openings in the air intake cowl
and flows axially across the outer cooling ribs of the motor frame. The fan wheel for the
external flow of cooling air is attached to the machine shaft.
The fan wheels are bidirectional.
Check the cooling effect below rated speed in the case of frequent switching or braking – or
if the speed is controlled continually below the rated speed.
Forced ventilation (optional): Type of cooling IC 416 in accordance with EN / IEC 60034-6
Cooling that does not depend on the speed is achieved by means of a unit that is
independent of the motor operating state (forced ventilation). This unit is closed to the
outside by a fan cover. It has its own main drive with fan impeller which creates the cooling
air flow required for cooling the motor.
3.3.3.2

Machines without a fan (optional)

Surface cooling by free convection: Cooling method IC 410 according to EN / IEC 60034-6
Figure 3-1
1LE5, 1PC4 shaft height 315/355
Operating Instructions, 10/2020, A5E41454666A
IC410
Description
3.3 Installation
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics sd 1pc4

Table of Contents