H8GN
Characteristics
Timer function
Accuracy of
operating time and
setting error
(including
temperature and
voltage effects)
Insulation resistance
Dialectic strength
Noise immunity
Static immunity
Vibration resistance
b a o
es s a ce
Malfunction
Destruction
S oc
Shock resistance
es s a ce
Malfunction
Destruction
Life expectancy
e e pec a cy
Mechanical
Electrical
Ambient
b e
Operating
t
temperature
t
Storage
Ambient humidity
EMC
Approved standards
Case color
Enclosure ratings
Weight
6
Signal start:
0.03%
30 ms max.
Power-ON start:
0.03%
50 ms max.
100 MΩ min. (at 500 VDC)
1,500 VAC, 50/60 Hz for 1 min between output terminals and non-current-carrying
metal parts
510 VAC, 50/60 Hz for 1 min between current-carrying terminals (except output
terminals) and non-current-carrying metal parts
1,500 VAC, 50/60 Hz for 1 min between output terminals and current-carrying
terminals (except output terminals)
500 VAC, 50/60 Hz for 1 min between communications terminals and current-carrying
terminals (except output terminals)
1,000 VAC, 50/60 Hz for 1 min between contacts not located next to each other
Square-wave noise by noise simulator;
480 V (between power terminals),
8 kV (malfunction),
15 kV (destruction)
10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min
10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h
2
100 m/s
, 3 times each in six directions
2
300 m/s
, 3 times each in six directions
10 million operations
100,000 operations min. (3 A at 250 VAC, resistive load)
–10 C to 55 C (with no icing or condensation)
–25 C to 65 C (with no icing or condensation)
25% to 85%
(EMI):
Emission Enclosure:
(EMS):
Immunity ESD:
Immunity RF-interference:
Immunity Conducted
Disturbance:
Immunity Burst:
Immunity Surge:
UL508, CSA C22.2 No.14
Conforms to EN61010-1/IEC61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P 100 (Finger Protection)
Rear section: Gray smoke; Front section: N1.5 (black)
Panel surface:
IP66 and NEMA Type 4X (indoors)
Rear case:
IP20
Terminal block:
IP20
Approx. 80 g
600 V (between input terminals)
EN61326 Class A
EN61326
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
EN61000-4-3:
10 V/m (Amplitude-modulated,
80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated,
900 MHz
5 MHz) (level 3)
EN61000-4-6:
3 V (0.15 to 80 MHz) (level 2)
EN61000-4-4:
2 kV power-line (level 3);
1 kV I/O signal-line (level 4);
1 kV communications-line (level 3)
EN61000-4-5:
1 kV between lines
(power and output lines) (level 3);
2 kV between grounds
(power and output lines) (level 3)