Fault Code Causes and Possible Solutions

Code
Fault
Description
0
No Fault
Fan is operating as
expected
1
Modbus
Inconsistent Modbus
Timeout
RTU communication
between control and
drive resulting in
incorrect fan operation
2
NOT USED
3
Motor Over
Internal motor
Temperature
temperature exceeds
maximum value
resulting in reduced fan
speed or shutdown
4
Drive Over
Internal VFD
Temperature
temperature exceeds
maximum value
resulting in reduced fan
speed or shutdown
5
Bus Over
Internal VFD voltage is
Voltage
higher than expected
resulting in fan
shutdown
6
Bus Under
Internal VFD voltage is
Voltage
lower than expected
resulting in fan
shutdown
7
Phase Over
Current is higher than
Current
expected on at least
one phase of supply
power resulting in fan
shutdown
8
Microcontroller
Microcontroller
High Temp
temperature exceeds
maximum value
resulting in reduced fan
speed or shutdown
9
Overspeed
Motor speed is
Fault
greater than maximum
allowable speed
resulting in reduced fan
speed or shutdown
26
Overhead Ceiling Fans
Possible Cause(s)
-
1. Loose CAT-5e cable connections
2. Unshielded or damaged CAT-5e cables
and RJ45 splitters
3. Incorrect network biasing settings
4. Incorrect low voltage wiring on euro
connector
5. Incorrect supply power applied to VFD
6. Supply power phase imbalance
Ambient temperature too high at the ceiling
Ambient temperature too high at the ceiling
Incorrect supply voltage
1. Incorrect supply voltage
2. Rapid power-cycling at circuit breaker
1. Incorrect supply power
2. Supply power phase imbalance
Ambient temperature too high at the ceiling
1. Incorrect blade count and/or fan size
selected in control
2. Wind gusts in building
Solution
-
1. Verify that all CAT-5e cable connections
are fully seated and secure
2. Replace cables with the provided
networking components (green shielded
CAT-5e cables and black shielded 3-way
RJ45 splitters) or components that
comply with specifications on page 15
3. Refer to Fan Networking instructions on
pages 16-18
4. Refer to Fan Networking instructions on
pages 16-18
5. Verify that supply voltage is within +/-
10% of the VFD's rated voltage
6. Verify that current is consistent across all
phases of supply power
Allow motor to cool before increasing speed
or restarting fan
Allow VFD to cool before increasing speed
or restarting fan
Verify that supply voltage is within +/- 10%
of the VFD's rated voltage
1. Verify that supply voltage is within +/-
10% of the drive's rated voltage
2. After turning power off, wait 30-60
seconds before turning power back on
1. Verify that supply power meets all power
quality requirements on page 14 and that
supply voltage is within +/- 10% of the
drive's rated voltage
2. Verify that current is consistent across all
phases of supply power
Allow VFD to cool before increasing speed
or restarting fan
1. Set fan size and blade count to match
physical product using instructions in the
control manual
2. Close overhead doors, etc. or relocate fan
®