Communication Wiring; With Pre-Built Cat-5E Cable - Greenheck DC Installation, Operation And Maintenance Manual

Overhead ceiling fans
Table of Contents

Advertisement

Communication Wiring

POWER SOURCE
IMPORTANT: DC fans must be installed with the
L1
supplied CAT-5e communication cable or shielded
N
CAT-5e (by others) that complies with the following
GROUND
specifications. Cable must be twisted pair, shielded
26 AWG CAT-5e cable with a drain wire and must be
GREEN
compliant with ISO 11801. Cable must use shielded
WHITE
RJ45 connectors with a soldered drain and wiring
BLACK
configuration must follow EIA/TIA T568B wiring pinout.
CHASSIS GROUND
Individual CAT-5e cable lengths must not exceed 200 ft.
in order to prevent network communication issues.

With Pre-Built CAT-5e Cable

Required Loose Components (Included):
• Shielded CAT-5e Control Cable (1)
Required Components from Bag # 918341:
• M4x10 Machine Screw (3)
Hardware/Tools Needed (Not Included):
• 1/8 in. Slotted Screwdriver
1. Connect the fan's communication wiring pigtail
JUNCTION BOX
to the open side of the 5-position euro connector
PER
installed on the universal mount. Make sure that
the wire colors are installed as shown below.
CHASSIS GROUND
LDED TWISTED PAIR CAT-5e CONNECTION
TO NEXT FAN
(IF APPLICABLE)
O CONTROL
UPPER SAFETY CABLE
CABLE CLAMP SADDLE
LIVE END
LOWER SAFETY CABLE
®
POWER WIRING
COMMUNICATION WIRING
BROWN/WHITE (24v)
BROWN (G)
BLUE (DATA+)
BLUE/WHITE (DATA-)
ORANGE (ENABLE)
NOTE:
REMOVE FACTORY WIRED JUMPER
BETWEEN BROWN (G) AND ORANGE
(ENABLE) TERMINALS IF USING RELAY.
RELAY NOT INCLUDED WITH FAN
2. Plug one end of the shielded CAT-5e control cable
that was previously routed to the fan's mounting
location into the 2-way RJ45 splitter located at the
universal mount. The cable can be plugged into
any open receptacle on the splitter.
SHIELDED TWISTED PAIR CAT-5e CONNECTION
3. Feed any loose communication wiring inside the
cavity of the universal mount or back down the
downtube to ensure it does not prevent the mount
cover from being installed.
4. Identify the desired location for installation of the
fan control and run the remainder of the shielded
CAT-5e control cable to this location.
5. Secure the shielded CAT-5e control cable to the
building structure to ensure it does not interfere
with fan performance. To prevent communication
issues, do not coil excess control cable or route
control cable with power wiring.
6. If one control source will be used to operate
multiple fans, the fans can be daisy-chained
together to create a network using the following
instructions.
a. Connect a shielded CAT-5e control cable to
the first fan in the daisy-chain using steps 1-3
above.
b. Plug an additional CAT-5e control cable into the
2-way RJ45 splitter located at the top of the
downtube on the first fan. Connect the other
end of this CAT-5e cable into the 2-way splitter
on the next fan.
MOUNT COVER
c. Repeat step 6b. for subsequent fans until all
fans in the chain are connected in series.
FAN 1
CONTROL
TO NEXT FAN
(IF APPLICABLE)
TO CONTROL
FAN 2
MOTOR, HUB AND VFD ASSEMBLY
Overhead Ceiling Fans
B
B
B
B
O
15