2. OUTDOOR FAN MOTOR
AC MOTOR
motor model:
9K/12K--
Main winding resistance:Black-Red 263Ω±15%;
Auxiliary winding resistance:Red-Blue 503Ω±15%;
motor model:
18K--
Main winding resistance:Black-Red 178Ω±15%;
Auxiliary winding resistance:Red-Blue 161.5Ω±15%;
motor model:
24K--
Main winding resistance:White-Black 81.84Ω±15%;
Auxiliary winding resistance:
Black-Blue
Black-Red
Yellow-Red
C
O
M
P
O
N
E
N
T
S
C
O
M
P
O
N
E
N
T
S
YDK25-6H3(YDK25-6H)
DG13Z1-75
Y6S643C252G
21.32Ω±15%;
24.03Ω±15%;
48.36Ω±15%;