14.2 Error codes
The following is the fault code table of outdoor.
Fault
Fault Description
code
Outdoor ambient
1
temperature sensor fault
Outdoor coil temperature
2
sensor fault
The unit over-current turn
3
off fault
4
EEprom Data error
Cooling freezing
protection(the indoor coil
temperature is too low) or
5
heating overload(indoor
coil temperature is too
high)
6
Motor blockage protection
H
O
O
T
I
N
G
H
O
O
T
I
N
G
Sheet 1 Outdoor Error Code
Possible Reason of Abnormality
1.The outdoor ambient temperature
sensor connect loose;
2.The outdoor ambient temperature
sensor is failure;
3.The sampling circuit is failure.
1.The outdoor coil temperature sensor
connect loose;
2.The outdoor coil temperature sensor
is failure;
3.The sampling circuit is failure
1.Control board current sampling
circuit is failure;
2.The current is over high because of
the supply voltage is too low;
3.The compressor is blocked;
4. Overload in cooling mode;
5.Overload in heating mode
1.EE components is failure;
2.EE components control circuit
failure;
3.EE components insert incorrect.
1.The indoor unit can not blow air
normally;
2.The room temperature is too low in
cooling mode or the room
temperature is too high in heating;
3.The filter is dirty;
4.The duct resistance is too high to
result in low air flow;
5.The setting fan speed is too low;
6. The indoor unit is not standard
installed, air inlet is too near with air
outlet .
1.Outdoor ambient temperature
sensor fault;
2. Outdoor coil temperature sensor
fault;
3.Outdoor control board fault.
How to Deal With
1.Reconnect the outdoor ambient
temperature sensor;
2.Replace the outdoor ambient temp.
sensor components;
3.Replace the outdoor control board
components.
1.Reconnect the outdoor coil
temperature sensor;
2.Replace the outdoor coil
temperature sensor components;
3.Replace the outdoor control board
components.
1. Replace the electrical control board
components;
2. Normally protection;
3. Replace the compressor ;
4. Please see the Note 3 ;
5. Please see the Note 4.
1.Replace the EE components;
2.Replace the outdoor control
board components;
3.Reassembly the EE components.
1.Check the indoor fan, indoor fan
motor and evaporator whether
normally;
2. Normally protection;
3.Clean the filter;
4.Check the volume control
valve,duct length etc;
5.Set the speed with high speed;
6.Reinstall the indoor unit refer to
the user manual to change the
distance between the indoor unit
and the wall or ceiling.
1.Replace outdoor ambient
temperature sensor;
2.Replace outdoor coil temperature
sensor;
3.Replace Outdoor control board.