Thermocouple Input Data Type/Format; Data Type; Factory Calibrate; Sensor Writeable - Omega SP-005 User Manual

Thermocouple and rtd smart probe
Table of Contents

Advertisement

5.1.2

Thermocouple Input Data Type/Format

The SP-005 supports extended configuration and provides factory calibration. All data values are returned as 32-bit
floating point values.
7
6
Smart
Sensor
Sensor
Writeable
5.1.2.1
0
0

Data Type

The 4-bit Data Type field determines the type of data of the specific sensor.
5.1.2.2

Factory Calibrate

The Factory Calibrate bit is used during factory calibration. If set, the factory calibration attributes are applied to the
sensor reading before the sensor scaling. If clear, not factory calibration attributes are applied. If the sensor does not
support factory calibration the Factory Calibrate bit is ignored and will always read as 0.
5.1.2.3

Sensor Writeable

If the Sensor Writeable bit is set the sensor value may be overwritten with a preset value. This capability is useful in
sensors such as up/down counters, where a preset, or possibly a zero value must be written to the sensor value.
5.1.2.4

Smart Sensor

5.1.3
Refer to the Smart Sensor Device Interface documentation.

Thermocouple Configuration

7
Available
Assigned
5.1.3.1
0

Sensor Type / Range

5.1.3.2

Apply Scaling

For more information on Gain and Offset, refer to the Smart Sensor Manual. If set, the user defined Offset and Gain
values will be used to adjust the sensor reading:
Thermocouple Input Data Type
5
Factory
Reserved
Calibrate
?
Thermocouple Configuration
6
5
Apply
Scaling
*
?
Sensor Type
Sensor Input Type (Range)
0x00
Type J
0x01
Type K
0x02
Type T
0x03
Type E
0x04
Type N
0x05
Reserved
0x06
Type R
0x07
Type S
0x08
Type B
0x09
Type C
Result = (Raw Reading * Gain) + Offset
4
3
0
4
3
Lock
?
Measurement Type
0x20
0x20
0x20
0x20
0x20
0x20
0x20
0x20
0x20
0x20
2
1
Data Type
0x06 == FLOAT
2
1
Sensor Type (Range)
See Below
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
Temperature (°C)
0
0
14 |
P a g e

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sp-005-1