Cross Section Area Of Wire For Main Power And On/Off Capacities; When Power Is Supplied Separately; Connect To Branch Box (Pac-Mk·bc); Connect To Connection Kit (Pac-Lv11M) - Mitsubishi Electric PUMY-P250YBM Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P250YBM:
Table of Contents

Advertisement

Cross section area of Wire for Main Power and ON/OFF capacities

9-2-2.
<When power is supplied separately>
Model
PUMY-P250YBM
Outdoor unit
PUMY-P300YBM
<When power is supplied from the outdoor unit>
Model
PUMY-P250YBM
Outdoor unit
PUMY-P300YBM
*1 A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2 In multi-phase appliances, the colour of the neutral conductor of the supply cord, if any, shall be blue.
<Indoor units> When power is supplied to indoor unit and outdoor unit separately
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 14)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit
Type 1
MSZ-AP·VG, MSZ-EF·VG-E2/ER2/ET2, MSZ-EF·VGK-E1/ER1/ET1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
Type 2
MSZ-FH·VE2
Type 3
Branch box (PAC-MK·BC)

Connect to Connection kit (PAC-LV11M)

Indoor unit
Type 4
MSZ-AP·VG, MSZ-EF·VG-E2/ER2/ET2, MSZ-EF·VGK-E1/ER1/ET1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
Type 5
MSZ-FH·VE2
Type 6
Connection kit (PAC-LV11M)
Connect to CITY MULTI
Indoor unit
Type 7
PEFY-P·VMA3-E, PEFY-P·VMA(L)-E1
Type 8
PEFY-P·VMHS-E-F, PEFY-P40–140VMHS-E
Type 9
PEFY-M·VMA(2)(L)-A, PEFY-P·VMA(L)-E3
PMFY-P·VBM-E, PLFY-EP·VEM-E, PLFY-P·VFM-E, PEFY-P·VMS1(L)-E, PCFY-P·VKM-E, PKFY-P·VKM-E,
Type 10
PFFY-P·VCM-E, PKFY-P·VLM-E/ET, PLFY-M·VEM-E/ET, PLFY-P·VEM-E
Type 11
PLFY-P·VEM-PA
Type 12
PLFY-P·VLMD-E, PEFY-P·VMR-E-L/R, PFFY-P·VKM-E2, PFFY-P·VLEM-E, GUF-RD(H)4, PEFY-P·VMH-E/E2
Type 13
PEFY-P200/250VMHS-E
Type 14
PEFY-P·VMX(L)-E(1)
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
Condition PLFY-VBM × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
16 A breaker (Tripping current = 8 × 16 A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type 1) + V2 × (Quantity of Type 2) + V2 × (Quantity of Type 3) + ··· + V2 × (Quantity of Type 14)
+ V3 × (Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec. or less
100 or less
100 mA 0.1 sec. or less
Wire thickness
1.5 mm
2
2.5 mm
2
4.0 mm
2
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
ple, use wiring such as YZW.
5. Install an earth longer than other cables.
OCH760
Minimum Wire Cross-sectional area (mm²)
Power supply *2
3N~ 380-400-415 V 50 Hz
3N~ 380-400-415 V 50 Hz
Minimum Wire Cross-sectional area (mm²)
Power supply *2
3N~ 380-400-415 V 50 Hz
3N~ 380-400-415 V 50 Hz
Minimum wire thickness (mm
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
V3
48
56
66
Main Cable
Ground
4.0
4.0
6.0
6.0
Main Cable
Ground
6.0
6.0
6.0
6.0
)
2
Ground-fault interrupter *1
Ground
1.5
20 A current sensitivity *3
2.5
30 A current sensitivity *3
4.0
40 A current sensitivity *3
113
Breaker for Wiring *1
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
Breaker for Wiring *1
Breaker for Current Leakage
40 A
40 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
Local switch (A)
Breaker for wiring
Capacity
Fuse
16
16
25
25
32
32
V1
V2
7.4
2.4
6.8
5.1
3.0
V1
V2
7.4
6.8
2.4
3.5
V1
V2
38.0
1.6
26.8
18.6
3.0
19.8
2.4
17.1
0
0
13.8
4.8
38.0
2.4
Sample chart
6000
600
60
10
1
0.1
0.01
1
2
3
4
Rated Tripping current (x)
cord (design 60245 IEC57). For exam-
(NFB)
20
30
40
SAMPLE
6
8
10
20
C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents