Wiring Of Main Power Supply And Equipment Capacity - Mitsubishi Electric CITY MULTI PURY-P-THMU-A Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

3 Transmission booster [Fig. 11..]
Max transmission cable length (M-NET cable): 1 L
Remote controller cable length:
1
If the length exceeds 10 m [32 ft], use 1.25 mm
within the total extended length and the longest remote length.

11.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)
[Fig. 11.4.1]
B
T(S)HMU: 3~208-230V
Y(S)HMU: 3~460V
L
, L
, L
1
2
3
B
~208–230V
L
, L
1
2
A Switch (Breakers for wiring and current leakage)
D Pull box
Thickness of wire for main power supply, ON/OFF capacities
Model
Unit combination
PURY-P72THMU(-BS)
PURY-P96THMU(-BS)
PURY-P120THMU(-BS)
PURY-P72THMU(-BS)
PURY-P144TSHMU(-BS)
PURY-P72THMU(-BS)
PURY-P96THMU(-BS)
Outdoor unit
PURY-P168TSHMU(-BS)
[PURY-P·
PURY-P72THMU(-BS)
T(S)HMU-A]
PURY-P96THMU(-BS)
PURY-P192TSHMU(-BS)
PURY-P96THMU(-BS)
PURY-P120THMU(-BS)
PURY-P216TSHMU(-BS)
PURY-P96THMU(-BS)
PURY-P120THMU(-BS)
PURY-P240TSHMU(-BS)
PURY-P120THMU(-BS)
PURY-P72YHMU(-BS)
PURY-P96YHMU(-BS)
PURY-P120YHMU(-BS)
PURY-P72YHMU(-BS)
PURY-P144YSHMU(-BS)
PURY-P72YHMU(-BS)
Outdoor unit
PURY-P96YHMU(-BS)
PURY-P168YSHMU(-BS)
[PURY-P·
PURY-P72YHMU(-BS)
Y(S)HMU-A]
PURY-P96YHMU(-BS)
PURY-P192YSHMU(-BS)
PURY-P96YHMU(-BS)
PURY-P120YHMU(-BS)
PURY-P216YSHMU(-BS)
PURY-P96YHMU(-BS)
PURY-P120YHMU(-BS)
PURY-P240YSHMU(-BS)
PURY-P120YHMU(-BS)
Indoor unit
1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For
example, use wiring such as YZW.
6. A switch with at least  mm [1/8 in] contact separation in each pole shall be provided when the Air Conditioner is installed.
Warning:
Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly,
heating or fire may result.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
Some installation sites may require attachment of a ground leakage breaker for the inverter. If a ground leakage breaker is not installed, there is a danger
of electric shock.
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
0
+ L
+ L
+ L
+ L
11
12
13
14
2 L
+ L
+ L
+ L
+ L
11
12
13
14
3 L
+ L
+ L
+ L
11
12
13
15
4 L
+ L
+ L
+ L
, L
17
16
14
15
,
10 m [32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
2
A
C
Ground
F
A
E
E
E
Ground
Ground
Ground
B Breakers for current leakage
E Indoor unit
Minimum wire thickness
(mm
[AWG])
2
Main cable
Branch
-
5.3 [10]
-
-
13.3 [6]
-
-
21.2 [4]
-
5.3 [10]
-
5.3 [10]
-
13.3 [6]
-
5.3 [10]
-
13.3 [6]
-
13.3 [6]
-
21.2 [4]
-
13.3 [6]
-
21.2 [4]
-
21.2 [4]
-
-
2.1 [14]
-
-
3.3 [12]
-
-
5.3 [10]
-
2.1 [14]
-
2.1 [14]
-
3.3 [12]
-
2.1 [14]
-
3.3 [12]
-
3.3 [12]
-
5.3 [10]
-
3.3 [12]
-
5.3 [10]
-
5.3 [10]
-
0.41 [22]
0.41 [22]
+ L
200 m [656 ft] (1.25 mm
[AWG 16])
2
16
17
+ L
200 m [656 ft] (1.25 mm
[AWG 16])
2
16
18
200 m [656 ft] (1.25 mm
2
[AWG 16])
+ L
+ L
+ L
200 m [656 ft] (1.25 mm
15
14
16
18
[AWG 16] shielded cable and calculate the length of that portion (L
2
F'
D
E
Ground
C Outdoor unit
F BC controller (standard or main)
Breaker
Switch (A)
for wiring
(NFB)(A)
Ground
Capacity
Fuse
5.3 [10]
30
30
13.3 [6]
40
40
21.2 [4]
50
50
5.3 [10]
30
30
5.3 [10]
30
30
13.3 [6]
40
40
5.3 [10]
30
30
13.3 [6]
40
40
13.3 [6]
40
40
21.2 [4]
50
50
13.3 [6]
40
40
21.2 [4]
50
50
21.2 [4]
50
50
2.1 [14]
15
15
3.3 [12]
20
20
5.3 [10]
25
25
2.1 [14]
15
15
2.1 [14]
15
15
3.3 [12]
20
20
2.1 [14]
15
15
3.3 [12]
20
20
3.3 [12]
20
20
5.3 [10]
25
25
3.3 [12]
20
20
5.3 [10]
25
25
5.3 [10]
25
25
0.41 [22]
15
15
[AWG 16])
2
15
F' BC controller (sub)
Breaker for current leakage
30
30 A 30 mA or 100 mA 0.1 sec. or less
40
40 A 100 mA 0.1 sec. or less
50
50 A 100 mA 0.1 sec. or less
30
30 A 30 mA or 100 mA 0.1 sec. or less
30
30A 30 mA or 100 mA 0.1 sec. or less
40
40 A 100 mA 0.1 sec. or less
30
30 A 30 mA or 100 mA 0.1 sec. or less
40
40 A 100 mA 0.1 sec. or less
40
40 A 100 mA 0.1 sec. or less
50
50 A 100 mA 0.1 sec. or less
40
40 A 100 mA 0.1 sec. or less
50
50 A 100 mA 0.1 sec. or less
50
50 A 100 mA 0.1 sec. or less
15
15 A 30 mA or 100 mA 0.1 sec. or less
20
20 A 30 mA or 100 mA 0.1 sec. or less
25
25 A 30 mA or 100 mA 0.1 sec. or less
15
15 A 30 mA or 100 mA 0.1 sec. or less
15
15 A 30 mA or 100 mA 0.1 sec. or less
20
20 A 30 mA or 100 mA 0.1 sec. or less
15
15 A 30 mA or 100 mA 0.1 sec. or less
20
20 A 30 mA or 100 mA 0.1 sec. or less
20
20 A 30 mA or 100 mA 0.1 sec. or less
25
25 A 30 mA or 100 mA 0.1 sec. or less
20
20 A 30 mA or 100 mA 0.1 sec. or less
25
25 A 30 mA or 100 mA 0.1 sec. or less
25
25 A 30 mA or 100 mA 0.1 sec. or less
15
20 A 30 mA 0.1 sec. or less
and L
) as
18
Maximum
Current(A)
24.0
36.0
45.7
24.4
24.4
36.7
24.4
36.7
36.7
46.7
36.7
46.7
46.7
10.8
16.3
20.6
11.0
11.0
16.6
11.0
16.6
16.6
21.0
16.6
21.0
21.0
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents