5.1 Precautions for Laying Optical Fiber Cables

1) The distance between stations varies depending on the type of optical
fiber cable used.
SI type optical fiber cable
(Old type: A-2P-$)
SI type optical fiber cable
SI (H-PGF) type optical fiber cable
QSI type optical fiber cable
2) When connecting an optical fiber cable, the following restrictions on the
bending radius must be observed.
Cable type
Type
SI (old)
A
B
C
D
SI
A
B
C
D
SI
A
(H-PCF)
B
D
QSI
A
B
C
D
(Type) A: Indoor use standard
C: Outdoor use standard
Type
L type
H type
Allowable bending radius
φ 2.8mm area [mm (in.)]
----- -
50 (1.97)
85 (3.35)
50
85 (3.35)
140 (5.51)
----- -
50 (1.97)
60 (2.36)
50
60 (2.36)
110 (4.33)
----- -
45 (1.77)
45
100 (3.94)
50
100 (3.94)
----- -
50 (1.97)
60 (2.36)
50
60 (2.36)
140 (5.51)
A
Distance between stations (m)
Connector A [mm (in.)]
CA9003
CA7003
45 (1.77)
----- -
30 (1.18)
----- -
----- -
30 (1.18) 30 (1.18)
B: Indoor use reinforced
D: Outdoor use reinforced
Module front
r
11
500 (1640.5 ft.)
300 (984.3 ft.)
500 (1640.5 ft.)
1000 (3281 ft.)
1000 (3281 ft.)
CA7005
DL-72ME
----- -
----- -
----- -
----- -
----- -
35 (1.38)
----- -
----- -
----- -