Common Specifications for General-purpose Slaves

4-1
Common Specifications for General-purpose Slaves
4-1-1

Current Consumption and Weight

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The following table lists specifications which are common to all General-pur-
pose Slaves. For details of specifications for each Slave, refer to the following
Slave specifications pages.
Item
Communications power
11 to 25 V DC (Supplied from the communications con-
supply voltage
nector.)
Internal power supply
20.4 to 26.4 V DC (24 V DC, –15 to +10%)
voltage
I/O power supply voltage
20.4 to 26.4 V DC (24 V DC, –15 to +10%)
±1.5 kV
Noise immunity
Vibration resistance
10 to 55 Hz, 1.0-mm double amplitude
Shock resistance
200 m/s
Dielectric strength
500 V AC (between isolated circuits)
Insulation resistance
20 MΩ min. at 250 V DC (between isolated circuits)
Ambient temperature
0 to 55°C
Ambient humidity
35% to 85%
Operating atmosphere
No corrosive gases
Storage temperature
–20 to 65°C
Mounting
M4 screw mounting or DIN 35-mm track mounting
Mounting strength
50 N
Track direction: 10 N
Screw tightening torque
M2 (Communications connector):
M3 (Power supply, I/O terminals):
M4 (Mounting Unit):
The following table lists the current consumption, weight, and connector lock
strength for basic Slaves.
Model
Communications
power supply
DRT1-ID08(-1)
30 mA max.
DRT1-ID16 (-1)
30 mA max.
DRT1-OD08(-1)
30 mA max.
DRT1-OD16 (-1)
30 mA max.
DRT1-MD16
25 mA max.
DRT1-ID16T(-1)
30 mA max.
DRT1-ID16TA(-1)
50 mA max.
DRT1-OD16T(-1)
30 mA max.
DRT1-OD16TA(-1)
50 mA max.
DRT1-MD16T(-1)
30 mA max.
DRT1-MD16TA(-1)
50 mA max.
DRT1-ID32ML(-1)
50 mA max.
DRT1-OD32ML(-1)
90 mA max.
Specifications
Pulse width: 0.1 to 1 μs
p-p
Pulse rise time: 1 ns
(via noise simulator)
2
Internal power
supply
50 mA max.
50 mA max.
50 mA max.
50 mA max.
45 mA max.
90 mA max.
(Same as communica-
tions power supply)
90 mA max.
(Same as communica-
tions power supply)
90 mA max.
(Same as communica-
tions power supply)
(Same as communica-
tions power supply)
(Same as communica-
tions power supply)
Section 4-1
0.25 to 0.3 N⋅m
0.3 to 0.5 N⋅m
0.6 to 0.98 N⋅m
Weight
135 g max.
170 g max.
140 g max.
180 g max.
170 g max.
315 g max.
315 g max.
315 g max.
315 g max.
315 g max.
315 g max.
110 g max.
100 g max.