2. Detailed Settings Function
2. Detailed Settings Function
List of Detailed Setting Items
Item code
Item
10
Type
11
Indoor unit capacity
System address
12
13
Indoor unit address
Group control address
14
Automatic stop time after
operation start
18
*Can be set in 5-minute
units.
OFF reminder function
35
for when weekly timer is
used
N
. o
0030
Air-to-Water (W1) (Setting at shipment)
80 (Type 80)
0012
0016 125 (Type 125)
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0030 Unit No. 30
0099 Not set (Setting at shipment)
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0064 Unit No. 64
0099 Not set (Setting at shipment)
0000 Individual (1:1 = Indoor unit with no group wiring) (Setting at shipment)
0000 Function disabled
0001 Stops automatically 5 minutes after operation starts.
0002 Stops automatically 10 minutes after operation starts.
0123 Stops automatically 615 minutes after operation starts.
0124 Stops automatically 620 minutes after operation starts.
0125 Stops automatically 625 minutes after operation starts.
None
0000
0001 Only stop time setting is enabled.
5 - 5