16. Troubleshooting Guide
Alarm code
F03
Alarm meaning
Abnormal refrigerant sensor 2 (E3)
Alarm conditions
A/D step is 10 steps or less (short circuit).
A/D step is 1014 steps or more (open circuit).
Possible Cause
Faulty connector connection
Faulty sensor
Faulty indoor unit PCB
Check
Measure the sensor resistance. Check that the sensor is operating normally.
Use a remote controller monitor or PC monitor to check the temperature that is
recognized by the microcomputer.
Alarm code
F10
Alarm meaning
Abnormal water inlet sensor (TA)
Alarm conditions
A/D step is 10 steps or less (short circuit).
A/D step is 1014 steps or more (open circuit).
Possible Cause
Faulty connector connection
Faulty sensor
Faulty indoor unit PCB
Check
Measure the sensor resistance. Check that the sensor is operating normally.
Use a remote controller monitor or PC monitor to check the temperature that is
recognized by the microcomputer.
Alarm code
F11
Alarm meaning
Abnormal water outlet sensor 2 (BL)
Alarm conditions
A/D step is 10 steps or less (short circuit).
A/D step is 1014 steps or more (open circuit).
Possible Cause
Faulty connector connection
Faulty sensor
Faulty indoor unit PCB
Check
Measure the sensor resistance. Check that the sensor is operating normally.
Use a remote controller monitor or PC monitor to check the temperature that is
recognized by the microcomputer.
2 - 15