Installing the Gateway
September 2020
Table 3-1: Emerson 1410S Gateway Power
Gateway version
Input and output connections
The Gateway is designed to be powered by 24 VDC (nominal) Class 2 supply and requires
350 mA of current.
The wiring should include an external power shut-off switch or circuit breaker positioned
near the Gateway.
The terminals on this connector can accommodate wires from 24 AWG to 12 AWG; 18
AWG wire is recommended. Tighten screws to 4.4 to 5.3 l bf-in (0.5 to 0.6 Nm).
In ambient temperatures greater than +60 °C, use wire rated for at least 5 °C above the
maximum ambient temperature.
Note
Using an uninterruptible power supply (UPS) is recommended to ensure availability during
power failure.
NOTICE
The Emerson 781S was designed for use with the Emerson 1410S Gateway and should
only be connected to the Emerson 1410S and/or other Emerson Gateway products.
Table 3-2: Emerson 781S Smart Antenna Power
Emerson Smart Antenna
model version
Input voltage
Power consumption
Radio protocol
EIRP (Max)
Antenna options
Input and output connections In: DC power (2-wire)
3.3

Mounting the Emerson 1410S2 Gateway

Find a location where the Gateway has convenient access to the host system network
(process control network).
22
(continued)
Non-barrier
In: DC power (2-wire, 1 connection)
Out: DC Power (2-wire, 2 connections)
I/O: RS-485 (2-wire, 2 connections)
781SA
10.5 to 30V VDC
0.25 W
®
IEC 62591 (WirelessHART
)
Meets all industrial environment requirements of EN61326.
Maximum deviation less than one percent span during EMC
disturbance.
Integrated omni-directional antenna
I/O: RS-485 (2-wire)
Reference Manual
00809-0600-4410
Barrier
781SC
0.30 W
IEC 62734 (ISA100)