2.3.11
Web page usage
It is not recommended that users stay logged on to a single page or a large number of
users on multiple pages for long periods of time. This additional loading can slow the flow
of data. By default, the Gateway logs users out after a long period of time with no activity.
2.3.12
Resetting to factory defaults
If the user name, password, or IP address of the Gateway is lost, the Gateway can be
restored to factory defaults using the procedure below.
Note
Following this procedure will cause the network to reform and all configuration
parameters will be reset to factory defaults. Once the Gateway is reset, the user is strongly
recommended to change the default password to maintain system security.
Procedure
1. Turn off power to the Gateway.
2. Locate the Reset switch.
3. Slide the switch to the "ON" position.
4. Reconnect the Gateway; turn power on to the Gateway.
5. Let the Gateway completely boot up (approximately three minutes).
6. Turn off power to the Gateway again.
7. Return the Reset switch to the "OFF" position.
8. Mount and reconnect the Gateway; restore power to the Gateway.
9. Verify the Reset switch is in the "OFF" position.
Emerson 1410S/781S
For the Emerson 1410S2 modular housing, the switch is located inside the Gateway
housing cover on the DIP switch panel board. The reset switch is labeled switch 4.
During this time, the red reset light on the front of the unit will be on.
The Gateway will now be programmed back to factory defaults including IP
addresses. See
Initial connection: Web browser returns "page not found"
default IP addresses.
Configuration
September 2020
for factory
19