A/C Evaporator Installation; D2/D4 Heater Installation; A/C Hose Connections And Routing - Trane Thermo King TriPac EVOLUTION Installation Manual

Auxiliary heating and cooling temperature management system
Table of Contents

Advertisement

T T i i p p s s F F o o r r a a S S u u c c c c e e s s s s f f u u l l I I n n s s t t a a l l l l a a t t i i o o n n

A/C Evaporator Installation

Always keep A/C system fittings capped and sealed until the installation of the refrigeration hoses.
Determine the best location for the A/C evaporator inside the sleeper, typically under the bunk.
Verify there is no interference with any OEM electrical wiring, internal supports, etc. before drilling any mounting
holes.
The evaporator should be mounted directly onto the floor mat inside the sleeper by using the supplied template to
locate the drain and mounting holes.
Always install the drain valves (kazoos) onto evaporator drain tubes securely with hose clamps.
The A/C vents should be located and installed to provide maximum air circulation in the sleeper such as: LOW (floor
level), MEDIUM (above lower bunk level) or HIGH (above upper bunk level).
All mounting holes must be sealed with silicone caulk to prevent moisture or exhaust fumes from entering the
sleeper.
All edges of access holes made in fiberglass and wood composite floors must be sealed correctly with fiberglass
cloth and resin.

D2/D4 Heater Installation

Determine the best location of the heater inside the sleeper, typically under the bunk. Allow clearance for
dismantling for service.
Install heater so it will maintain a minimum distance of 2.00 inches (50.8 mm) from any heat sensitive or flammable
material.
Heater must be mounted on a flat horizontal surface.
Heater must be installed flush with the floor pan (i.e. sheet metal, fiberglass, etc.) to ensure proper sealing of the
mounting plate and gasket.
All edges of access holes made in fiberglass and wood composite floors must be sealed correctly with fiberglass
cloth and resin.
Outside air intake and exhaust hoses must be installed correctly for the heater to operate safely.
Exhaust hose should be mounted slightly downwards to help drain off condensation.
Install exhaust hose so it will maintain a minimum distance of 2.00 inches (50.8 mm) from any heat sensitive or
flammable material.
Inside air inlet and outlet ducts must be installed correctly for the heater to operate safely.
Pulse fuel pump must be installed at a 15 to 35 degree angle from horizontal to operate correctly.
Fuel pickup tube must be installed correctly in the fuel tank or the heater will not operate.
Fuel line from the pickup tube to the fuel pump to the heater should be routed at a continuous rise.
Use a hose cutter or sharp knife to cut plastic fuel lines. Do not use a wire cutter as this will pinch the plastic fuel line
closed.
Do not route electrical wires, harness or battery cables together with fuel lines.
BEFORE operating the heater, the fuel lines must be bled of air using the Heater Priming Harness (204-1144) or
damage to the fuel pump will result.
The Diagnostic Code Reader (204-1143) must be used to setup and operate the heater in the run-in mode.

A/C Hose Connections and Routing

Always keep A/C system fittings capped and sealed until the installation of the refrigeration hoses.
Only cut refrigerant hoses with the correct hose cutting tool (204-677). NEVER USE A SAW!
Always use the correct hose fitting tool (204-1045) when assembling refrigeration hoses.
Always lubricate hose fittings with PAG 100 refrigerant oil (2030502) when assembling to refrigeration hoses.
Always install and lubricate O-rings with PAG 100 refrigerant oil (2030502) when connecting refrigeration hose
fittings to component connection fittings.
12
TK 55676-19-IM-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents