● Change/activate settings
● Change password (p10061 ... p10063)
Safety Integrated
Function Manual, (FHS), 11/2009, 6SL3097-4AR00-0BP0
– Change settings
You can select this button and enter the TM54F password in order to edit the
configuration data. The button function changes to "Activate settings".
– Activate settings
This function activates your parameter settings and initiates calculation of the actual
CRC and the corresponding transfer to the target CRC.
The parameters are activated after restart, and you are requested to carry out the
acceptance test.
A message is output requesting you to save the project and then restart the system.
It is also required to carry out an acceptance test.
In order to change the password, enter the old password (factory setting: 0) and then
enter and confirm the new password.
7.3 Commissioning TM54F by means of STARTER/SCOUT
Commissioning