Approved Venting Method 2: Through the Ceiling 
 
 
 
 
 
 
 
 
 
 
 
 
 
Storm Collar 
 
 
Roof Flashing 
 
 
 
Ceiling Support Box 
 
 
 
 
 
Prefabricated chimney systems must conform to UL‐103HT (2100 °F) for the U.S. and ULC‐S629 (650°C) for 
Canada. 
This wood burning unit is only listed for installation with 6.0" diameter chimney connector and chimney systems. 
Installing this unit on prefabricated chimneys larger than 6.0" diameter will result in decreased draft and the potential 
for poor unit performance. 
Follow all venting system manufacturer's installation requirements and required clearances. 
Use three sheet metal screws at each single wall chimney connector joint (check manufacturer's 
recommendations when double wall chimney connector is used). 
Drill three holes in the flue collar of the unit and attach the chimney connector to the unit using sheet metal screws 
(holes should be pre‐drilled in flue collar from factory). 
Properly attach the prefabricated chimney system to the home in strict accordance with the prefabricated chimney 
system manufacturer's instructions. 
The overall length of the chimney connector must not exceed 8.0 ft.  In the case of cathedral ceilings, the 
prefabricated chimney system should extend to 8.0 ft. from the top of the unit if using single wall chimney 
connector pipe. If necessary to run longer than 8.0 ft. of chimney connector pipe, double wall black chimney 
connector pipe must be used.
Special adapters and slip connectors are available to eliminate the need to cut single wall chimney connector. 
Double wall chimney connector must be used with these slip connectors, as it cannot be trimmed to length. 
 
Please Note: Installation diagrams are for reference purposes only and are not drawn to scale, nor meant to be used as plans 
for each individual installation.  Please follow all venting system requirements, maintain the required clearances to 
combustibles, and follow all local codes 
13
INSTALLATION 
10 ft. 
 
 
Termination Cap 
The 10‐3‐2 Rule: The chimney system 
must terminate 3.0 ft. above the point 
where its centerline passes through the 
roof AND the chimney must terminate 
2.0 ft. above any part of the dwelling  
within a 10 ft. radius of the chimney. 
Class A Chimney System  
 
Chimney Connector 
(Single or Double Wall) 