RDR8S and I32O16 Modules
Impaired Performance Conditions
Condition
Unit environment not as specified
Unit power and grounding not as specified
Cable length or type not as specified

Testing Procedure

 To check for proper operation of the RDR8S:
1. Verify that the "POWER" LED is ON.
2. Verify that the "STATUS" LED flashes once per second.
3. Verify that the "XMIT" and "RCV" LEDs blink.
4. Present a valid card to each reader connected to the RDR8S reader interface
and then verify that access is granted (green lamp lights).
5. Present an invalid card to each reader connected to the RDR8S reader
interface and then verify that access is denied (red lamp lights).
 To check for proper operation of the I32O16:
1. Verify that the "POWER" LED is ON.
2. Verify that the "STATUS" LED flashes once per second.
3. Verify that the "XMIT" and "RCV" LEDs blink.
4. Change the state of any input and verify change of state.
5. Change the state of any output and verify change of state.

Replacement Parts

There are no serviceable components inside the RDR8S or I32O16 plastic enclosure.
Generic replacement terminal blocks can be ordered if lost. For more information on
the parts listed, refer to the applicable catalog page.
Fuses
The RDR8S and I32O16 have no replaceable fuses.
24-10489-0 Rev. B
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2010 Johnson Controls, Inc.
Hardware Installation
Information Location
See "Technical Specifications" on page 21.
See "Power Supply" on page 12 and
"Ground" on page 16.
See "Cable Requirements" on page 11.